Electrical Application Details for App #: M358845
Premises: 195 CHRYSTIE STREET MANHATTAN BIN: 1005719     Block: 426   Lot: 29
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 195 CHRYSTIE ST Census Tract:   36.01 Health Area:  6500
2ND FL Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   RIVINGTON STREET,    STANTON STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/22/2014 12:55 PM
Application Entered:   09/22/2014 Job Start Date:   09/22/2014
Last Change:   08/22/2025 Job End Date:   09/30/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DHANESHWAR BISSOON       On     02/04/2025      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $176.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BERNARDO AGUERO
Owner Business Name: METROPOLITAN DESIGN INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    20  40    12  40  19         
Buildings Total 20  40    12  40     19           
Total Units : 131 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/22/2014 Notice: 1 - FIRST NOTICE 02/05/2025
Power Issued: 09/22/2014 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M358845
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/04/2025 02/05/2025 DWB V (42) (5)
INSPECTION COMMENTS: ATOI INSPECTION INCOMPLETE, CONTRACTOR NEED TO ADD, ELE-EQUIP MISSING FROM APPS. OBJECTION ISSUED.

OBJECTION FOR APPLICATION #: M358845
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 002)201.8(7) RECEPTACLE NOT GFCI PROTECTED/INSTALLED OUTSIDE EDGE OF THESINK/BASIN/ AT PANTRY AREA.
OPEN 02/04/2025 02/04/2025
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 002)110.16, ARC FLASH LABEL NOT PROVIDED AT NEW ELECTRICAL EQUIPINSTALLED/ THRU-OUT.
OPEN 02/04/2025 02/04/2025
 
003 (247) SIMULTANEOUS OPENING OF POLES
(FLOOR: 002)MULTI WIRE BRANCH CIRCUIT WITH SHARE NEUTRAL SIMULTANEOUS TRIP (NOTHANDLE TIES)210.4 (B)/ AT PANELS THRU-OUT.
OPEN 02/04/2025 02/04/2025
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 002) 110.12(A) KO MISSING AT PANELS.
OPEN 02/04/2025 02/04/2025
 
005 (999) OTHER
(ALL FLOORS)CONTRACTOR NEED TO ADD, ELE-EQUIP MISSING FROM APPS, PANELS, 4-225AMP TOTAL 4 INSTALLED,- FEEDERS, 2 SET OVER 1/0 TO 250 MCM, TOTAL 2SET INSTALLED,- 5 SET UP TO #2, TOTAL 5 SET INSTALLED,- FLRDESCRIPTION, 2 FLR, HEATERS, TOTAL 1, TOTAL 1 INSTALLED.
OPEN 02/04/2025 02/04/2025



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back