Electrical Application Details for App #: M358734
Premises: 333 HUDSON STREET MANHATTAN BIN: 1010374     Block: 597   Lot: 55
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 333 HUDSON ST Census Tract:   37
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   VANDAM STREET,    CHARLTON STREET
Status:   C - JOB IS SIGNED OFF 10/12/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   09/19/2014 Job Start Date:   09/19/2014
Last Change:   10/12/2016 Job End Date:   02/13/2015
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     09/30/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011542 Licensee Name: JOHN A LEE
Firm: 003240 Firm Name: J.A. LEE ELECTRIC, INC.
Firm Phone: 718-361-1907  Firm Address: 23-30 50TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $165.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52346     Submittal #: 14A0113  
Owner / Occup: CHRIS CRAWFORD
Owner Business Name: AT&T MOBILITY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/19/2014 Notice: C - CALL TO OFFICE 09/22/2016
Power Issued: 09/19/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 200 AMP METER AND DISCONECT FOR AT&TREVISED APPLICATION 2/13/14

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M358734
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/03/2014 10/14/2014 NRS V G (40) (4) Y
INSPECTION COMMENTS: END LINE BOX BONDING NOT INSPECTED
 
(2) 02/05/2015 02/12/2015 ECH J Y E (90) (0) Y
INSPECTION COMMENTS: FUSES AND GROUND NOT PER DRAWING
 
(3) 04/13/2015 04/17/2015 PHG J Y E (30) (0) Y
INSPECTION COMMENTS: DID NOT HAVE UPDATED PRINTS
 
(4) 10/30/2015 11/12/2015 CBK H X E (30) (0) Y
INSPECTION COMMENTS: DID NOT HAVE DRAWINGS
 
(5) 09/21/2016 09/22/2016 STP H X (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR SHOWED UP.
 
(6) 09/30/2016 10/04/2016 BMP C R (50) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M358734
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASE: NOT INSTALLED
RSLV 10/03/2014 10/03/2014 02/05/2015
 
002 (999) OTHER
BASE: SERVICE EQUIPMENT CORRODED FROM WATER DEIPPING FROM CEILINGPIPE. 110.12B
RSLV 10/03/2014 02/05/2015 04/13/2015
 
003 (999) OTHER
(ALL FLOORS)BASE: NOT INSTALLED PER ADVISORY BOARD DRAWING. AM.110.2B
RSLV 10/03/2014 10/30/2015 09/30/2016
 
004 ( 19) DEFECTIVE WIRING IS IN USE
BASE: IMPROPER TAP LUG MOUNTING IN END LINE BOX(USE OF BUS MOUNTINGSCREWS)
RSLV 10/03/2014 10/03/2014 02/05/2015