BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M358615
Premises: 314 EAST 41 STREET MANHATTAN BIN: 1080449     Block: 1333   Lot: 42
   
Application Completed and Certified

Filed: 314 E 41 ST Census Tract:   88 Health Area:  5000
3 FLOOR Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10017 Community Board:   106
DOB Cross Street(s):    2 AVENUE,    TUDOR CITY PLACE
Status:   C - JOB IS SIGNED OFF 04/20/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/16/2014 9:40 PM
Application Entered:   09/16/2014 Job Start Date:   09/19/2014
Last Change:   04/20/2015 Job End Date:   11/25/2014
Appointment Status:   
Last Inspection By:   FATA, LUIGI       On     03/25/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011785 Licensee Name: LEONID LADYZHENSKIY
Firm: 003593 Firm Name: FOREST BROOK ELEC'L CONTR
Firm Phone: 347-462-2606  Firm Address: 2906 SHELL ROAD 1ST FL INC BROOKLYN NY 11224 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WINER APPLEBY
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  305                 
Buildings Total                   
Total Units : 13 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/29/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:   GENERAL WIRING ON KITCHEN ONLY.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M358615
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/22/2015 01/29/2015 EDB A (50) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 03/25/2015 04/01/2015 LUF C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M358615
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANEL MULTIWIRE CKT: NO GROUPED, NO SIMULTITRIP 210.4
RSLV 01/22/2015 01/22/2015 03/25/2015
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
PANEL NO AFCI ON NEW LINES
RSLV 01/22/2015 01/22/2015 03/25/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back