BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M358610
Premises: 261 WEST 25 STREET MANHATTAN BIN: 1089820     Block: 775   Lot: 5
   
Application Completed and Certified

Filed: 261 W 25 ST Census Tract:   91 Health Area:  5200
7TH AVE. & 8TH AVE. Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 10/14/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/16/2014 5:55 PM
Application Entered:   09/16/2014 Job Start Date:   09/16/2014
Last Change:   10/14/2015 Job End Date:   09/15/2015
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     08/27/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $456.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRAD PASCARELLA
Owner Business Name: NATALI GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  250.00
B. Each Additional 10 Floors Or Less  2  166.00
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/29/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  DEVICE NO. PE1 & PE2

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M358610
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/23/2015 07/29/2015 PHG A (105) (4) Y
INSPECTION COMMENTS: 1P48266,1P48265
 
(2) 08/27/2015 10/14/2015 BMP C R (65) (0) Y
INSPECTION COMMENTS: REMEDIATION WAS NEEDED

OBJECTION FOR APPLICATION #: M358610
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
#14 WIRE USED FOR BOTH CAB LIGHTS.. 210.19
RSLV 07/23/2015 07/23/2015 08/27/2015
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
EMT PIPE FOR SW IN PIT NOT SUPPORTEDLIGHT SW IN PIT BOX NOT SUPPORTED
RSLV 07/23/2015 07/23/2015 08/27/2015
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
EMT IN MOTOR RM NOT SUPPORTED
RSLV 07/23/2015 07/23/2015 08/27/2015
 
004 (999) OTHER
TROUGH IN MOTOR RM BOTH 2" PIPES NOT BONDED.. 250.96
RSLV 07/23/2015 07/23/2015 08/27/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back