BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M358112
Premises: 228 EAST 6 STREET MANHATTAN BIN: 1006620     Block: 461   Lot: 22
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 228 E 6 ST Census Tract:   38 Health Area:  5800
ALL APARTMENTS Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):   TARAS SHEVCHENKO PLACE,    2 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/03/2014 3:21 PM
Application Entered:   09/03/2014 Job Start Date:   09/03/2014
Last Change:   08/22/2025 Job End Date:   04/21/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     04/15/2015      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  X - NOT REMOVED

License #: 010981 Licensee Name: VASILIOS BILLY TAKOS
Firm: 001408 Firm Name: TAKOS AND K ELECTRIC INC
Firm Phone: 718-472-1300  Firm Address: 38-58 11TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $912.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JONATHAN TABAK
Owner Business Name: AJT MANAGEMENT
Authorized Representative:  JONATHAN TABAK
Relationship To Owner:   SAME


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  19  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  20  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  ALL                28     
002  ALL                28     
003  ALL                28     
004  ALL                28     
005  ALL                28     
Buildings Total                   140      
Total Units : 140 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 21 #4-Wire 0 #10-Wire 0
Existing Meters 21 + New Meters 21 - Removed Meters 21 = Total Meters 21

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/03/2014 Notice: C - CALL TO OFFICE 04/24/2015
Power Issued: 09/03/2014 Response:  

Follow-Up:
Contractor's Comments:  INSTALLING NEW SERVICE EQUIPMENT, APARTMENT SUB-FEEDERS, PANELS AND 1 STOVE OUTLET IN EACH APARTMENT EXCEPT APARTMENT #9 DONE UNDER ANOTHER APPLICATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M358112
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/03/2014 12/09/2014 DNM P (60) (0) Y
INSPECTION COMMENTS: PANEL RISOR AND 1 NEW STORE RECEPTACLE CHANCED FUSES TO CIRCUIT BREAK BREAKER IN EACH APT SERVICE INSPECTED NEED ACCES TO APT INPECTED 1FL APT ONLY
 
(2) 02/27/2015 03/06/2015 EID A E (100) (1) Y
INSPECTION COMMENTS: 40 A LINE TI ELECTRIC STOVE FOR 16APTS. APT 1,4,9 AND 15 ARE EXISTING CONDITIONS
 
(3) 04/15/2015 04/24/2015 NRS A X G (45) (3) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M358112
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BASEMENT APT 1,4,9AND15: EX OVERFUSED AT 70A ON NEW SER (240.3) SER
OPEN 02/27/2015 04/15/2015
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BASE: 2 SETS OF 2.5" EMT AT G"X 2H" PULL BOXES # AT 'LB' ABOVE METERBANK
OPEN 04/15/2015 04/15/2015
 
003 (999) OTHER
BASE: 6'X12' PULL BOXES & 10'X10' SPLICE BOX 314.2 NOT SUPPORTED
OPEN 04/15/2015 04/15/2015
 
004 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
BASE: 1.5" 'LB' ABOVE METER BANK: LOOSE MECH. GROUND
OPEN 04/15/2015 04/15/2015