Electrical Application Details for App #: M358053
Premises: 31 WEST 12 STREET MANHATTAN BIN: 1009627     Block: 576   Lot: 56
   
Application Completed and Certified

Filed: 31 W 12 ST Census Tract:   63 Health Area:  5700
3W Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 03/05/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/02/2014 3:04 PM
Application Entered:   09/02/2014 Job Start Date:   09/02/2014
Last Change:   03/05/2015 Job End Date:   09/02/2016
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     02/19/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011681 Licensee Name: PAUL OLSEN
Firm: 004266 Firm Name: NASH ELECTRIC SERVICES IN
Firm Phone: 646-688-3350  Firm Address: 286 EAST 236TH STREET BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $142.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GIAMPAPA CHRISTOPHER
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3W  30  50  20               
Buildings Total 30  50  20                  
Total Units : 101 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/10/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M358053
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/29/2014 11/05/2014 FRI N (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW - CLAIMS TO HAVE CANCELED APPOINTMENT
 
(2) 11/17/2014 12/05/2014 FRI Z (0) (0) Y
INSPECTION COMMENTS: APPOINTMENT CANCELED BY CONTRACTOR
 
(3) 12/08/2014 12/16/2014 GYM N (25) (0) Y
INSPECTION COMMENTS: NO ACCESS APT 3W
 
(4) 02/04/2015 02/10/2015 DNM A (40) (5) Y
INSPECTION COMMENTS: NONE
 
(5) 02/19/2015 02/25/2015 DNM C R (20) (0) Y
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M358053
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANEL: CONDUCTORS ARE NOT PROPERLY CODED.. 210.53/0 CONDUCTORS ON LINE SIDE OF PANEL
RSLV 02/04/2015 02/04/2015 02/19/2015
 
002 (999) OTHER
PANEL: MULTIWRE BRANCH CIRCUITS NOT ON SINGLE TIE OR 2 POLE BREAKER210.4
RSLV 02/04/2015 02/04/2015 02/19/2015
 
003 (999) OTHER
BATHROOM: G.F.C.I. NOT PROVIDED FOR BATHROOM.. 210.8
RSLV 02/04/2015 02/04/2015 02/19/2015
 
004 (999) OTHER
KITCHEN: G.F.C.I.NOT PROVIDED FOR KITCHEN ISLAND.. 210.8
RSLV 02/04/2015 02/04/2015 02/19/2015
 
005 ( 19) DEFECTIVE WIRING IS IN USE
PANEL: DEFECTIVE WIRING IN USE #12 AWG FOR A/C IS ON 30 AMP CIRCUITBREAKER
RSLV 02/04/2015 02/04/2015 02/19/2015