BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M357513
Premises: 63 SPRING STREET MANHATTAN BIN: 1007554     Block: 496   Lot: 34
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 63 SPRING ST Census Tract:   43 Health Area:  6800
ALL FLOORS Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   CLEVELAND PLACE,    CROSBY STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/19/2014 5:48 AM
Application Entered:   08/19/2014 Job Start Date:   08/28/2014
Last Change:   08/22/2025 Job End Date:   02/27/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   URIM SYLA       On     02/10/2015      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  Y - PARTLY REMOVED

License #: 009908 Licensee Name: WILLIAM HINKE
Firm: 002281 Firm Name: AMKO ELEC CONST & MAINT I
Firm Phone: 718-440-5586  Firm Address: 4320 35TH STREET STE B LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $745.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 5 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JEFFREY SRULOWITZ
Owner Business Name: 63 SPRING/LAFAYETTE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  # 2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  2  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  9  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001           
002    18  30    18     
003    18  30    18     
004    18  30    18     
005    18  30    18     
ROF            18         
Buildings Total 82  129    35  76     42     35      
Total Units : 399 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 08/19/2014 Notice: 1 - FIRST NOTICE 02/13/2015
Power Issued: 08/19/2014 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M357513
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/29/2014 01/07/2015 NRS A E (120) (18) Y
INSPECTION COMMENTS: FLOOR DESCRIPTIONS & WORK DESCRIPTION IMPROPERLY FILLED IN
 
(2) 01/27/2015 01/30/2015 TOR Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 02/10/2015 02/13/2015 UMS A Y E (50) (1) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M357513
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BASE: INNER ELECTR.ROOM30A LAUNDRY RECE NOT AS PER
RSLV 12/29/2014 12/29/2014 02/10/2015
 
002 (279) WATER METER JUMPER IS MISSING/IMPROPER
BASE: MISSING
RSLV 12/29/2014 12/29/2014 02/10/2015
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
BASE: E.G.C. NEEDED BETWEEN 400A SERVICE SWITCH & TRIUGH ABOVE
RSLV 12/29/2014 12/29/2014 02/10/2015
 
004 (999) OTHER
BASE: NO TIE BREAKERS PROVIDED FOR MULTIWIRE CIRCUITS.(4) APT PANELS210.4
RSLV 12/29/2014 12/29/2014 02/10/2015
 
005 (999) OTHER
BASE: LAUNDRY E.G.C. IN APARTMEMT PANELS NOT AS PER 250.122
RSLV 12/29/2014 12/29/2014 02/10/2015
 
006 ( 42) BUSHINGS ARE MISSING OR LOOSE
BASE: APT.PANELS BOTTOM TROUGH
RSLV 12/29/2014 12/29/2014 02/10/2015
 
007 (145) APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED.
ALL FLOORS: LAUNDRY HEATERS
RSLV 12/29/2014 12/29/2014 02/10/2015
 
008 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
ALL FLOORS: BEDROOMS
RSLV 12/29/2014 12/29/2014 02/10/2015
 
009 (999) OTHER
ALL FLOORS: 3 HOLE DRYER RECES. 250.142(B)
RSLV 12/29/2014 12/29/2014 02/10/2015
 
010 (999) OTHER
ALL FLOORS: PENINSULA RECE NOT AS PER 210.52
OPEN 12/29/2014 02/10/2015
 
011 (999) OTHER
ALL FLOORS: COOKTOP DISCONNECT E.B.J NOT AS PER 250.122
RSLV 12/29/2014 12/29/2014 02/10/2015
 
012 (999) OTHER
ALL FLOORS: COOKTOP DISCONNECT E.G.C. DOUBLE LUG
RSLV 12/29/2014 12/29/2014 02/10/2015
 
013 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
ALL FLOORS: NOT FINISHED
RSLV 12/29/2014 12/29/2014 02/10/2015
 
014 (999) OTHER
ALL FLOORS: INSTANT HOT & WINE COOLER ON SMALL APPLIANCES CIRCUITS
RSLV 12/29/2014 12/29/2014 02/10/2015
 
015 (183) DISCONNECT IS NOT READILY ACCESSIBLE
ALL FLOORS: AIR HANDLER IN BATH CEILING
RSLV 12/29/2014 12/29/2014 02/10/2015
 
016 (999) OTHER
ALL FLOORS: NO COVER PLATE ON AIR HANDLER DISCONNECT. 404.9
RSLV 12/29/2014 12/29/2014 02/10/2015
 
017 ( 57) EXPOSED ARMORED CABLES ARE SUBJECT TO PHYSICAL DAMAGE
ALL FL: SMOKE DETECTOR & HALLWAY RECEPTACLE
RSLV 12/29/2014 12/29/2014 02/10/2015
 
018 (999) OTHER
ALL FL: MICROWAVE RECEPTACLE NOT AS PER 210.21
RSLV 12/29/2014 12/29/2014 02/10/2015
 
019 (999) OTHER
TEMP WIRING AND POWER IN GROUND FLOOR NOT REMOVED 590.3
OPEN 02/10/2015 02/10/2015