| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
8 |
# 2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
|
| D. Over 250 MCM |
2 |
500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
9 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BASE: INNER ELECTR.ROOM30A LAUNDRY RECE NOT AS PER |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 002 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER BASE: MISSING |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 003 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED BASE: E.G.C. NEEDED BETWEEN 400A SERVICE SWITCH & TRIUGH ABOVE |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 004 |
(999) |
OTHER BASE: NO TIE BREAKERS PROVIDED FOR MULTIWIRE CIRCUITS.(4) APT PANELS210.4 |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 005 |
(999) |
OTHER BASE: LAUNDRY E.G.C. IN APARTMEMT PANELS NOT AS PER 250.122 |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 006 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE BASE: APT.PANELS BOTTOM TROUGH |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 007 |
(145) |
APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED. ALL FLOORS: LAUNDRY HEATERS |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 008 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER ALL FLOORS: BEDROOMS |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 009 |
(999) |
OTHER ALL FLOORS: 3 HOLE DRYER RECES. 250.142(B) |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 010 |
(999) |
OTHER ALL FLOORS: PENINSULA RECE NOT AS PER 210.52 |
OPEN |
12/29/2014 |
02/10/2015 |
|
| |
| 011 |
(999) |
OTHER ALL FLOORS: COOKTOP DISCONNECT E.B.J NOT AS PER 250.122 |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 012 |
(999) |
OTHER ALL FLOORS: COOKTOP DISCONNECT E.G.C. DOUBLE LUG |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 013 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY ALL FLOORS: NOT FINISHED |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 014 |
(999) |
OTHER ALL FLOORS: INSTANT HOT & WINE COOLER ON SMALL APPLIANCES CIRCUITS |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 015 |
(183) |
DISCONNECT IS NOT READILY ACCESSIBLE ALL FLOORS: AIR HANDLER IN BATH CEILING |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 016 |
(999) |
OTHER ALL FLOORS: NO COVER PLATE ON AIR HANDLER DISCONNECT. 404.9 |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 017 |
( 57) |
EXPOSED ARMORED CABLES ARE SUBJECT TO PHYSICAL DAMAGE ALL FL: SMOKE DETECTOR & HALLWAY RECEPTACLE |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 018 |
(999) |
OTHER ALL FL: MICROWAVE RECEPTACLE NOT AS PER 210.21 |
RSLV |
12/29/2014 |
12/29/2014 |
02/10/2015 |
| |
| 019 |
(999) |
OTHER TEMP WIRING AND POWER IN GROUND FLOOR NOT REMOVED 590.3 |
OPEN |
02/10/2015 |
02/10/2015 |
|