BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M357483
Premises: 221 EAST 63 STREET MANHATTAN BIN: 1043863     Block: 1418   Lot: 11
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 225 E 63 ST Census Tract:   110 Health Area:  4900
9D,10F,11H,PHF,3E,3F,5J,9H Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):    3 AVENUE,    2 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/18/2014 1:26 PM
Application Entered:   08/18/2014 Job Start Date:   08/18/2014
Last Change:   08/22/2025 Job End Date:   08/22/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   URIM SYLA       On     04/16/2015      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 011834 Licensee Name: VINCENT LOMBARDOZZI
Firm: 003439 Firm Name: VTL ELECTRIC CO., CORP
Firm Phone: 347-223-8746  Firm Address: 104 SACKETT STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $296.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FRANK FRED
Owner Business Name: CP LLL AJ 63RD, LLC
Authorized Representative:  FRED FRANK
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  11  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
MZ3  3E  10               
MZ3  3F  10               
MZ5  5J               
MZ7  7B               
MZ7  7H               
MZ9  9D  10               
MZ9  9H  10               
M10  10F  14         
M11  11A  10               
M11  11H  12           
PEN  PHF  18  12         
Buildings Total 75  118  83  94              
Total Units : 375 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 04/21/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M357483
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/01/2014 10/09/2014 LBI V (60) (3) Y
INSPECTION COMMENTS: HAD TIME TO INSPECT 10F,11H AND PHF ONLY ALL COUNTS AS ORIGINALLY FILED ARE WRONG
 
(2) 02/27/2015 03/02/2015 LUF A X (60) (1) Y
INSPECTION COMMENTS: OBJECTIONS LOCATIONS ARE ABC FOLLOWED APARTMENTS 3E - 3F,7B 7H 9D 9H NO ACCESS TO 5J - 10F - 11A - 11H - PHF
 
(3) 04/16/2015 04/21/2015 UMS A Y (60) (1) Y
INSPECTION COMMENTS: 5J 10F 11A 11H PHF WERE INSPECTED

OBJECTION FOR APPLICATION #: M357483
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (229) SPLICE BOXES NOT ACCESSIBLE
PHF: OLD PANEL LOCATION/SPLICE BOX NOT ACCESSIBLE. 314.29
OPEN 10/01/2014 04/16/2015
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
10F,11H,PHF: IMPROPERLY INSTALLED/SIZED BONDING JUMPER BETWEEN OLD/NEW PANELS. 250.102E,TABLE 250.122
RSLV 10/01/2014 02/27/2015 04/16/2015
 
003 (999) OTHER
0F,11H,PHF: OPENINGS NOT SEALED IN OLD PANEL COVER. 110.2,408.7
OPEN 10/01/2014 04/16/2015
 
004 (229) SPLICE BOXES NOT ACCESSIBLE
SPLICE BOXES NOT ACCESSIBLE,OLD PANEL LOCATION SPLICE BOX NOTACCESSIBLE.. 314.29
OPEN 02/27/2015 04/16/2015
 
005 (999) OTHER
SPLICE BX NOT ACCESSIBLE NO SUFFICIENT ACCESS & WORKING SPACE PROVFOR ALL OLD PNLS WHICH ARE BEING USED AS SPLICE BX 110.26 31429
OPEN 04/16/2015 04/16/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back