BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M357424
Premises: 54 FRANKLIN STREET MANHATTAN BIN: 1001872     Block: 172   Lot: 30
   
Application Completed and Certified

Filed: 54 FRANKLIN ST Census Tract:   31 Health Area:  7700
FIRST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   LAFAYETTE STREET,    BENSON PLACE
Status:   C - JOB IS SIGNED OFF 07/15/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/15/2014 3:39 PM
Application Entered:   08/15/2014 Job Start Date:   08/15/2014
Last Change:   07/15/2015 Job End Date:   09/19/2014
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     07/02/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011616 Licensee Name: CESAR TIPIAN
Firm: 004145 Firm Name: C.T.C. ELEC'L CONTRS INC
Firm Phone: 347-810-9954  Firm Address: 435 AUSTIN PLACE, SUITE D BRONX NY 10455 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $173.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   ART GALLERY
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 54-56 MANAGEMENT CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1-200 AMPS, 1-100 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    21  44  21  51         
Buildings Total 21  44  21  51              
Total Units : 144 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/25/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PARTIAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M357424
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/08/2015 06/16/2015 BUR N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(2) 06/16/2015 06/25/2015 BUR A (50) (5) Y
INSPECTION COMMENTS: NONE
 
(3) 07/02/2015 07/09/2015 PHG C R (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M357424
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OFFICE: ART LIGHT FIXTURE NOT LISTED.. 410.06
RSLV 06/16/2015 06/16/2015 07/02/2015
 
002 (999) OTHER
OFFICE: RECEPTACLES RECESS INTO PLYWOOD WALL COMBUSTIBLE MATERIAL314.20
RSLV 06/16/2015 06/16/2015 07/02/2015
 
003 (999) OTHER
CELLAR: RECEPTACLE WITHIN 6' OF SINK NOT G.F.C.I.PROTECTED.. 210.8
RSLV 06/16/2015 06/16/2015 07/02/2015
 
004 (999) OTHER
CELLAR: FIRE PROOFING NOT PTOVIDED FOR CONDUITS GOING THROUGH BUILD-ING WALL AND SPACES.. 300.21
RSLV 06/16/2015 06/16/2015 07/02/2015
 
005 (999) OTHER
WASH ROOM: SWITCH IN WASHROOMNOT WET PROOFED.. 404.4
RSLV 06/16/2015 06/16/2015 07/02/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.