BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M357298
Premises: 214 EAST 34 STREET MANHATTAN BIN: 1088117     Block: 914   Lot: 36
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 222 E 34 ST Census Tract:   70 Health Area:  5800
BASE/ FIRST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):   QUEENS MIDTOWN TUNNEL EXIT,    2 AVENUE
Status:   C - JOB IS SIGNED OFF 01/28/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/12/2014 11:04 PM
Application Entered:   08/12/2014 Job Start Date:   08/15/2014
Last Change:   01/28/2016 Job End Date:   10/22/2014
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     10/07/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010473 Licensee Name: JERRY SPADARO
Firm: 003908 Firm Name: FIVE STARS ELEC'L CONTR'G
Firm Phone: 718-639-6862  Firm Address: 82-31 51ST AVENUE (NY), INC ELMHURST NY 11373 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $533.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   HAIR SALON
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JULIAN BEST
Owner Business Name: SOLA SALON
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  4  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  BASE  45  35    15  112  28  62         
002  1 FL  55  40    18  20         
Buildings Total 100  75    33  132     64           
Total Units : 404 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 05/14/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FILING FOR GENERAL WIRING IN BASEMENT AND FIRST FLOOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M357298
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/04/2015 03/10/2015 EDB V (40) (3) Y
INSPECTION COMMENTS: JOB NOT FINISH
 
(2) 03/30/2015 04/06/2015 GYM A Y (65) (2) Y
INSPECTION COMMENTS: NONE
 
(3) 05/11/2015 05/14/2015 ECH H X (35) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 08/17/2015 08/24/2015 NRS Z (0) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELED INSPECTION
 
(5) 09/09/2015 09/15/2015 NRS J Y (30) (0) Y
INSPECTION COMMENTS: NONE
 
(6) 10/07/2015 10/16/2015 PHG C R (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M357298
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
T-OUT: NO G.F.C.I. W/IN 6' FROM SINK.. 210.8
RSLV 03/04/2015 05/11/2015 09/09/2015
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
CEILING: OUTTET BOXES FOR TV NOT COVERED.. 314.25
RSLV 03/04/2015 03/04/2015 03/30/2015
 
003 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
CEILING: LIGHT FIXTURE NOT PROPERLY SECURED.. 410.30,36
RSLV 03/04/2015 09/09/2015 10/07/2015
 
004 (999) OTHER
BSMT,1ST FL: ALL AREAS WITH MC CABLE,BRANCH WIRING,OUTLET BOXES NOTBONDED.. ART.250.146 (ALL BOXES)
RSLV 03/30/2015 05/11/2015 09/09/2015
 
005 (999) OTHER
A) BSMT,1ST FL: ALL LIGHTS FIXTURE MC CABLE GREEN WIRES CUT OUTCABLE.. ART.110.2,250.146
RSLV 03/30/2015 09/09/2015 10/07/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back