| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
4 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 53) |
GFCI HAS NOT BEEN PROVIDED T-OUT: NO G.F.C.I. W/IN 6' FROM SINK.. 210.8 |
RSLV |
03/04/2015 |
05/11/2015 |
09/09/2015 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED CEILING: OUTTET BOXES FOR TV NOT COVERED.. 314.25 |
RSLV |
03/04/2015 |
03/04/2015 |
03/30/2015 |
| |
| 003 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER CEILING: LIGHT FIXTURE NOT PROPERLY SECURED.. 410.30,36 |
RSLV |
03/04/2015 |
09/09/2015 |
10/07/2015 |
| |
| 004 |
(999) |
OTHER BSMT,1ST FL: ALL AREAS WITH MC CABLE,BRANCH WIRING,OUTLET BOXES NOTBONDED.. ART.250.146 (ALL BOXES) |
RSLV |
03/30/2015 |
05/11/2015 |
09/09/2015 |
| |
| 005 |
(999) |
OTHER A) BSMT,1ST FL: ALL LIGHTS FIXTURE MC CABLE GREEN WIRES CUT OUTCABLE.. ART.110.2,250.146 |
RSLV |
03/30/2015 |
09/09/2015 |
10/07/2015 |