Premises: 245 WEST 25 STREET MANHATTAN BIN: 1014198     Block: 775   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 245 W 25 ST Census Tract:   91 Health Area:  5200
47 APARTMENTS Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 07/22/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/08/2014 4:36 PM
Application Entered:   08/08/2014 Job Start Date:   08/08/2014
Last Change:   07/22/2016 Job End Date:   08/07/2015
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     06/28/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011267 Licensee Name: ALEXANDER ABRAMOVICH
Firm: 002666 Firm Name: INTEGRAL ELECL PWR & CNTR
Firm Phone: 212-645-5528  Firm Address: 307 7TH AVENUE,SUITE 301 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $3,351.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL
Owner Business Name: NAFTALI GROUP
Authorized Representative:  MICHAEL WITEK
Relationship To Owner:   REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  2  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  48  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL          48             
LOB            57             
001      295  10  72  83             
002      236  57  67             
003      207  50  59             
004      180  44  50             
005      236  57  67             
006      236  57  67             
Buildings Total   1390  47  342  498                
Total Units : 2277 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 68 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/08/2014 Notice: C - CALL TO OFFICE 06/14/2016
Power Issued: 08/08/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PROVIDE NEW 2000 A SERVICE WITH RENOVATION OF 47 (FROM 68 )APARTMENTS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M357172
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/30/2014 01/12/2015 EID V G (210) (7) Y
INSPECTION COMMENTS: INSPECTED: FEEDER, PNL & BRANCH WIRING FOR APT 1D,1J,1K,1H,1N,1E,6C,3 L,5B, OTHER APT & SERVICE NOT READY FOR INSPECTION
 
(2) 06/13/2016 06/14/2016 TUR V X (65) (5)
INSPECTION COMMENTS: ONLY HAD TIME TO INSPECT SERVICE, CONTRACTOR NEEDS TO REQUEST MORE TIME FOR INSPECTION FOR ALL APARTMENTS IN BUILDING (6FLOORS) SOME PRE INSPECTED WITH OBJECTIONS OTHERS NOT INSPECTED AT ALL (HE ALSO HAS OTHER APPS HE NEEDS INSPECTED MUST REQUEST AT THAT TIME LISTED IN SCHEDULING NOTES MUST HAVE FULL ACCESS
 
(3) 06/28/2016 06/28/2016 BMP C R (105) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M357172
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)4J,1K,1D,1N,5B: PNL: SIMULTANEOUS TRIP NOT PROVIDED FOR MULTIWIRECRTS 210.4(B)
RSLV 12/30/2014 12/30/2014 06/28/2016
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)1D,1N,1M: PNL: ARCH FAULT PROF NOT PRO FOR ALL BRANCH CKT 210.12B
RSLV 12/30/2014 12/30/2014 06/28/2016
 
003 (999) OTHER
(ALL FLOORS) ALL: RECEP SET BACK IN COMBO MICRO 314.20
RSLV 12/30/2014 12/30/2014 06/28/2016
 
004 (999) OTHER
(ALL FLOORS) 6C,4J,1J: ONLY 1 CKT ON KITCHEN COUNTER 210.52(B3)
RSLV 12/30/2014 12/30/2014 06/28/2016
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) 3L: PNL NOT LABELLED/ NO DIRECTORY 408.4
RSLV 12/30/2014 12/30/2014 06/28/2016
 
006 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS)3L,1K: CKT SHARED FOR A/C LLOV TAPPE OF 220V CKT OF 220V CKT 110.2A
RSLV 12/30/2014 12/30/2014 06/28/2016
 
007 (999) OTHER
(ALL FLOORS) 1D,1M: MC PNL FEEDER EGC NOT BND TO PNL 250.146
RSLV 12/30/2014 12/30/2014 06/28/2016
 
008 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT)250.92(A) LOOSE LOCK NUTS THROUGH OUT INSTALLATION AND GROUND LUG ONFIRST SWITCH LOOSE HOUSE MAIN SWITCH
RSLV 06/13/2016 06/13/2016 06/28/2016
 
009 (135) DEFECTIVE GROUND ROD IS IN USE
(BASEMENT)250.52(A5) DEFECTIVE GROUND ROD IN USE NOT INSTALLED PROPERLY ANDNOT INSTALLED IN APPROVED MEANS (CONTRACTOR NEEDS TO BRING TOCOLLECTOR BAR AND SUGGEST THAT HE LABEL ALL POINTS ON BAR WITHDURABLE MEANS
RSLV 06/13/2016 06/13/2016 06/28/2016
 
010 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT)240.3 FUSE OVER SIZED IN HOUSE PANEL MAIN DISCONNECT 500AMP FUSE FOR500KCM
RSLV 06/13/2016 06/13/2016 06/28/2016
 
011 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(BASEMENT)320.40 ARMORED CABLES FOR FEEDERS TO APARTMENTS FOR FUTURE AND TEMPSNOT TERMINATED IN BOX MOUNTED AND LABELED
RSLV 06/13/2016 06/13/2016 06/28/2016
 
012 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(BASEMENT) 110.12(A) KNOCKOUTS OPEN MUST CLOSE
RSLV 06/13/2016 06/13/2016 06/28/2016