BIS Menu  |  Electrical Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M356201
Premises: 93 EAST 4 STREET MANHATTAN BIN: 1006221     Block: 446   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 99 E 4 ST Census Tract:   38 Health Area:  6500
2M Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 08/16/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/17/2014 1:07 PM
Application Entered:   07/17/2014 Job Start Date:   07/18/2014
Last Change:   08/16/2016 Job End Date:   09/18/2014
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     07/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012099 Licensee Name: ANTHONY DAVINO, JR
Firm: 003796 Firm Name: A.DAVINO ELEC'L CONT'G CO
Firm Phone: 212-964-9500  Firm Address: 10 EAST 39TH STREET, 12TH FL NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $64.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT LAVECHIA
Owner Business Name: MULBERRY GROUP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  125AMP #6AWG
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2M  21  12             
Buildings Total 21  12                
Total Units : 49 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/31/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SMALL APARTMENT REWIRE EXISTING RISER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M356201
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/28/2014 10/31/2014 NRS A (40) (6) Y
INSPECTION COMMENTS: EXISTING RISER NEW PANEL
 
(2) 07/29/2016 07/29/2016 CBK C R (45) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: M356201
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) 2M: FOR ALL NECESSARY CIRCUITS
RSLV 10/28/2014 10/28/2014 07/29/2016
 
002 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
(ALL FLOORS) 2M: IN PANEL ON 1 PF BRANCH CIRCUITS
RSLV 10/28/2014 10/28/2014 07/29/2016
 
003 (999) OTHER
(ALL FLOORS) 2M: A/C RECEPTACLES NOT T/R. 406.11
RSLV 10/28/2014 10/28/2014 07/29/2016
 
004 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS) 2M: 2 COUNTER G.F.C.I. BOXES ON STOVE SIDE
RSLV 10/28/2014 10/28/2014 07/29/2016
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) 2M: CONNECTOR IN G.F.C.I. BOX NEXT TO STOVE
RSLV 10/28/2014 10/28/2014 07/29/2016
 
006 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
(ALL FLOORS) 2M: COUNTER G.F.C.I. BOX NEXT TO STOVE
RSLV 10/28/2014 10/28/2014 07/29/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back