BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M356067
Premises: 14 EAST 53 STREET MANHATTAN BIN: 1088582     Block: 1288   Lot: 56
   
Application Completed and Certified

Filed: 510 MADISON AV Census Tract:   102 Health Area:  4800
52ND ST./30TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   THE GREATEST GOOD
DOB Cross Street(s):   EAST 52 STREET,    EAST 53 STREET
Status:   C - JOB IS SIGNED OFF 03/24/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/15/2014 11:29 AM
Application Entered:   07/15/2014 Job Start Date:   07/21/2014
Last Change:   03/24/2015 Job End Date:   10/21/2014
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     03/18/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010741 Licensee Name: ROBERT J PESTONE
Firm: 001118 Firm Name: P.E. STONE INC
Firm Phone: 212-334-1113  Firm Address: 50 WATTS STREET NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $284.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: THE GREATEST GOOD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
030    40  125    32  120          30 
Buildings Total 40  125    32  120               30 
Total Units : 347 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/23/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PES JOB NO. 14-106

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M356067
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/09/2014 12/15/2014 EID Z (0) (0) Y
INSPECTION COMMENTS: CANCELED BY OFFICE
 
(2) 12/17/2014 12/23/2014 EDB A (60) (5) Y
INSPECTION COMMENTS: NONE
 
(3) 03/18/2015 03/24/2015 EDB C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M356067
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
EL.RM: 30 KVA T-FMR NO OCP FOR LPL-30 B PANEL. 240.4,21
RSLV 12/17/2014 12/17/2014 03/18/2015
 
002 (999) OTHER
EL.RM: NO ARC FLASH WARNING ON NEW EQUIPMENT. 110.16
RSLV 12/17/2014 12/17/2014 03/18/2015
 
003 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
T-OUT: CEILING FLEX CORD USED FOR POWER TO SHADES. 400.8
RSLV 12/17/2014 12/17/2014 03/18/2015
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
T-OUT: OFFICE FURNITURE NOT PROPERLY GND. 250.112
RSLV 12/17/2014 12/17/2014 03/18/2015
 
005 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
T-OUT: CEILING SPLICE BOXES KO MISSING. 110.12A
RSLV 12/17/2014 12/17/2014 03/18/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back