BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355792
Premises: 72 GREENE STREET MANHATTAN BIN: 1079933     Block: 485   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 72 GREENE ST Census Tract:   49 Health Area:  6800
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   ELEVATOR REPLACEMENT
DOB Cross Street(s):   BROOME STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 07/12/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/08/2014 6:27 AM
Application Entered:   07/08/2014 Job Start Date:   07/09/2014
Last Change:   07/12/2016 Job End Date:   12/15/2014
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     07/09/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011480 Licensee Name: GREGORY J CARDILLO
Firm: 001965 Firm Name: NEAD ELECTRIC INC.
Firm Phone: 212-764-2752  Firm Address: 530 WEST 50TH STREET NEW YORK NY 10019 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $90.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ASB 72-76 GREENE ST
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                 
Buildings Total                 
Total Units : 11 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/10/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  7276GRG3-AZ-REPLACE PANEL "RP-ELEV" INSTALL NEW ELEVATOR DISCONNECT SWITCH. INSTALL NEW PIT LIGHTS & PIT RECEPTACLES. INSTALL (2) NEW CORRIDOR FIXTURES.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355792
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/04/2015 03/10/2015 NRS A (70) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 07/09/2016 07/12/2016 STP C R (30) (0)
INSPECTION COMMENTS: PASS VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: M355792
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BASE: SERVICE ROOM #1. 2.5 EMT FEEDING ELEV.EQUIPMENT EXITS TROUGHCOVER.. 110.3
RSLV 03/04/2015 03/04/2015 07/09/2016
 
002 (999) OTHER
(ALL FLOORS)BASE: E.B.J. NOT SIZED FOR TAP CONDUCTORS AS PER 250.122
RSLV 03/04/2015 03/04/2015 07/09/2016
 
003 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(ALL FLOORS) BASE: 200A ELEV.PANEL (RP - ELEV)
RSLV 03/04/2015 03/04/2015 07/09/2016
 
004 (999) OTHER
(ALL FLOORS)BASE: 200A ELEV.PANEL NO TIE BREAKER & GROUPING FOR MULTIWIRE CIRCS210.4
RSLV 03/04/2015 03/04/2015 07/09/2016
 
005 (999) OTHER
(ALL FLOORS)BASE: FEEDER TAP FOR ELEVATOR EQUIP.MORE THAN 25'.. 240.21
RSLV 03/04/2015 03/04/2015 07/09/2016
 
006 (999) OTHER
(ALL FLOORS)BASE: 2.5" EMT NOT SUPPORTED IN CORRIDOR & PANEL ROOM(RP-ELEV)358.30
RSLV 03/04/2015 03/04/2015 07/09/2016
 
007 (999) OTHER
(ALL FLOORS) BASE: ELEVATOR DISCONNECT NOT MARKED.. 110.22
RSLV 03/04/2015 03/04/2015 07/09/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.