Electrical Application Details for App #: M355714
Premises: 75 GRAND STREET MANHATTAN BIN: 1077408     Block: 229   Lot: 22
   
Application Completed and Certified

Filed: 75 GRAND ST Census Tract:   47 Health Area:  6800
APT.3W Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   WOOSTER STREET,    GREENE STREET
Status:   C - JOB IS SIGNED OFF 12/15/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/03/2014 12:19 PM
Application Entered:   07/03/2014 Job Start Date:   07/03/2014
Last Change:   12/15/2014 Job End Date:   09/01/2014
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     11/20/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011399 Licensee Name: JEFF SKOWRONSKI
Firm: 002489 Firm Name: INTER CONNECTION ELETRIC
Firm Phone: 718-748-9800  Firm Address: 209 GRANITE AVE STATEN ISLAND NY 10303 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $99.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLARD BOEPPLE
Owner Business Name: ANDREWS BUILDING CORP.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003  3W  67  55    45  67         
ROF              12         
Buildings Total 67  55    45  67     14           
Total Units : 248 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/17/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355714
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/03/2014 09/08/2014 EID V (55) (3) Y
INSPECTION COMMENTS: COULD NOT INSP LED DRIVERS FOR BATHROOMS AND COMPRESSORS ON ROOF
 
(2) 10/08/2014 10/17/2014 NRS A Y (40) (3) Y
INSPECTION COMMENTS: NONE
 
(3) 11/20/2014 12/02/2014 ECH C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M355714
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
3W A/C UNITS OCP DEVICES NOT SIZED AS PER MAN. SPEC: ALL (110.3(B))
RSLV 09/03/2014 09/03/2014 10/08/2014
 
002 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
3W KITCHEN LED TRANS WIRING NOT PROPERLY TERM. (110.14)
RSLV 09/03/2014 10/08/2014 11/20/2014
 
003 (229) SPLICE BOXES NOT ACCESSIBLE
3W LED DRIVERS FOR 2 BATH ROOMS. NOT ACCESSIBLE (314.29)
RSLV 09/03/2014 09/03/2014 10/08/2014
 
004 (999) OTHER
ROOF: NI IN USE COVER ON G.F.C.I
RSLV 10/08/2014 10/08/2014 11/20/2014
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF: A/C E.G.C.NOT AS PER 250.122
RSLV 10/08/2014 10/08/2014 11/20/2014
 
006 (999) OTHER
3W: CPMPRESSPR OCPD NOT PER INSTRUCTIONS. 440.22(C)
RSLV 10/08/2014 10/08/2014 11/20/2014