BIS Menu  |  Certs. Occupancy  |  Comments  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355700
Premises: 5 UNIVERSITY PLACE MANHATTAN BIN: 1080105     Block: 548   Lot: 4
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 5 UNIVERSITY PL Census Tract:   59 Health Area:  5700
1ST FLOOR/ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Special Place Name:   NYU WEINSTEIN HALL
DOB Cross Street(s):   WASHINGTON SQUARE NORTH,    WASHINGTON MEWS
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/03/2014 10:26 AM
Application Entered:   07/03/2014 Job Start Date:   07/03/2014
Last Change:   08/22/2025 Job End Date:   07/03/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     10/08/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010763 Licensee Name: STEPHEN ROSTOWSKY
Firm: 002342 Firm Name: ROCKMOR ELEC. ENTERPR INC
Firm Phone: 718-633-3700  Firm Address: 1042 39TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $132.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CAFETERIA
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TURNER CONSTRUCTION
Authorized Representative:  RANIA BATAINEH
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4 #2; 1 #6 GROUND
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  225 AMP PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    71    37           
ROF                       
Buildings Total 71    38                
Total Units : 119 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 10/17/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  JOB #40407

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355700
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/08/2014 10/17/2014 NRS V (90) (8) Y
INSPECTION COMMENTS: 30A STEAM TABLE,PANEL FEEDERS & OCPD,LIGHTS & ROOF NOT INSPECTED

OBJECTION FOR APPLICATION #: M355700
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1FL: NEUTRALS DOUBLE LUGGED IN BOTH PANELS
OPEN 10/08/2014 10/08/2014
 
002 ( 40) LOCKNUTS ARE MISSING OR LOOSE
1FL: OLD RELOCATED PANEL
OPEN 10/08/2014 10/08/2014
 
003 ( 42) BUSHINGS ARE MISSING OR LOOSE
1FL: OLD RELOCATED PANEL
OPEN 10/08/2014 10/08/2014
 
004 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
1FL: 1900 BOX IN COLD TALE FOR G.F.C.I.RECE
OPEN 10/08/2014 10/08/2014
 
005 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
1FL: G.F.C.I.WALL RECE UNDER LIGHT SWITCH
OPEN 10/08/2014 10/08/2014
 
006 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
1FL: WALKIN FRIDGE LIGHT DOES NOT WORK
OPEN 10/08/2014 10/08/2014
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1FL: PULL BOX ABOVE OLD RELOCATED PANEL
OPEN 10/08/2014 10/08/2014
 
008 (999) OTHER
1FL: MC FEEDERS ARMOR REACHES INTO PULL BOX BEYOND PLASTIC BUSHINGABOVE OLD PANEL. 110.3
OPEN 10/08/2014 10/08/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.