BIS Menu  |  Plumb. Inspections  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355457
Premises: 69 CLINTON STREET MANHATTAN BIN: 1004232     Block: 349   Lot: 29
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 69 CLINTON ST Census Tract:   30.01 Health Area:  6600
2A,2B,2D,3A,3B,4A,5A,5C,4B,3C Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   STANTON STREET,    RIVINGTON STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/26/2014 11:00 PM
Application Entered:   06/26/2014 Job Start Date:   06/26/2014
Last Change:   08/22/2025 Job End Date:   06/26/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     06/10/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 012089 Licensee Name: PEDRO M ABREU
Firm: 004413 Firm Name: JAMCOB ELECTRIC LLC
Firm Phone: 347-577-6644  Firm Address: 1420 WHITE PLAINS ROAD BRONX NY 10462 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $222.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LIONEL NAZARIAN
Owner Business Name: 69 CLINTON NPG LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2A  12  12           
002  2B  12  12           
002  2D  12  12           
003  3A  12  12           
003  3B  12  12           
004  4A  12  12           
005  5A  12  12           
005  5C  12  12           
Buildings Total 96  96  40            19      
Total Units : 259 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/17/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  APARTMENTS WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355457
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/31/2015 04/07/2015 BUR V (60) (5) Y
INSPECTION COMMENTS: ONLY APT 4A INSPECTED
 
(2) 04/14/2015 04/20/2015 BUR N (20) (0) Y
INSPECTION COMMENTS: CALL AND WAIT,CONTRACTOR NO SHOW
 
(3) 05/06/2015 05/13/2015 WYF N (25) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR,SAID HE COULD NOT MAKE APPOINTMENT
 
(4) 06/10/2015 06/17/2015 NRS V Y (50) (5) Y
INSPECTION COMMENTS: NEED CUT SHEET FOR COOK TOP 2400W SINGLE POLE 20A BREAKER 3C INSPECTED ONLY

OBJECTION FOR APPLICATION #: M355457
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
LIVING RM: AC RECEPTACLE NOT TAMPER RESISTANT.. 406.11
RSLV 03/31/2015 03/31/2015 06/10/2015
 
002 (999) OTHER
KITCHEN: RECEPTACLE WITHIN 6' FROM SINK NOT G.F.C.I. PROTECTED210.8A
RSLV 03/31/2015 03/31/2015 06/10/2015
 
003 (999) OTHER
BED CLOSET: CLOSET HAS OPEN INCANDESENT FIXTURE LAMP NOT PROTECTED
RSLV 03/31/2015 03/31/2015 06/10/2015
 
004 (999) OTHER
BATH: LIGHT FIXTURE TRIM IN BATH RM NOT WET RATED.. 410.4
RSLV 03/31/2015 03/31/2015 06/10/2015
 
005 (999) OTHER
BED RM: NO DISCONNECTING MEANS PROVIDED FOR FIXED SPACE HEATER424.19
OPEN 03/31/2015 06/10/2015
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
3C
OPEN 06/10/2015 06/10/2015
 
007 (999) OTHER
3C: RECES NOT T/R.. 406.11
OPEN 06/10/2015 06/10/2015
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
3C: COOK TOP POWER CORD CONNECTOR BX 90* USED
OPEN 06/10/2015 06/10/2015
 
009 ( 53) GFCI HAS NOT BEEN PROVIDED
3C
OPEN 06/10/2015 06/10/2015
 
010 (145) APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED.
ELECTRIC HEATER IN BEDR
OPEN 06/10/2015 06/10/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.