BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355305
Premises: 112 BOWERY MANHATTAN BIN: 1003127     Block: 239   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 112 BOWERY Census Tract:   41 Health Area:  6800
CEL,GND,002,003,004 Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   HESTER STREET,    GRAND STREET
Status:   C - JOB IS SIGNED OFF 03/09/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/23/2014 11:26 PM
Application Entered:   06/23/2014 Job Start Date:   06/23/2014
Last Change:   03/09/2016 Job End Date:   06/22/2015
Appointment Status:   
Last Inspection By:   URIM SYLA       On     03/08/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009789 Licensee Name: LAWRENCE J NELSON
Firm: 001794 Firm Name: NELSON & TOM MAINT INC DB
Firm Phone: 212-233-0622  Firm Address: 29 EAST BROADWAY SUITE 201 NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $693.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COMMERICAL STORES
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHING LAU
Owner Business Name: SUN REALTY 112 BOWERY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  6  200A FIRE PUMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  5  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    15    15         
GND    10  25    10  10             
002    10  25    10  10             
003    10  25    10  10             
004    10  25    10  10             
ROF              50         
Buildings Total 48  115    48  48     65           
Total Units : 324 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 5 #10-Wire 0
Existing Meters 3 + New Meters 5 - Removed Meters 3 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/23/2014 Notice: 1 - FIRST NOTICE 01/26/2016
Power Issued: 06/23/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SERVICE AND GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355305
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/19/2016 01/26/2016 UMS V (50) (4)
INSPECTION COMMENTS: INSPECTION COMPLETE
 
(2) 03/08/2016 03/09/2016 UMS C R (45) (0)
INSPECTION COMMENTS: UPDATE IN OFFICE. AS PER URM

OBJECTION FOR APPLICATION #: M355305
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) FIRE PUMP SERVICE SWITCH NOT MARKED PROPERLY AMEND 695
RSLV 01/19/2016 01/19/2016 03/08/2016
 
002 (999) OTHER
(BASEMENT)ELECTRICAL PANELS MISSING ARC FLASH WARNING SIGNS NEC 110.16
RSLV 01/19/2016 01/19/2016 03/08/2016
 
003 (999) OTHER
(BASEMENT) ALL PANELS MISSING DIRECTORY 408.4
RSLV 01/19/2016 01/19/2016 03/08/2016
 
004 (999) OTHER
(GROUND FLOOR)EXIT SIGNS BY FRONT ENTRANCES NOT SUPPORTED A.NEC 410.30
RSLV 01/19/2016 01/19/2016 03/08/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back