BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355246
Premises: 229 WEST 28 STREET MANHATTAN BIN: 1014255     Block: 778   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 229 W 28 ST Census Tract:   95 Health Area:  5200
CELLAR, 1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 05/17/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/23/2014 10:21 AM
Application Entered:   06/23/2014 Job Start Date:   06/23/2014
Last Change:   05/17/2018 Job End Date:   03/30/2015
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     02/06/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011998 Licensee Name: VADIM OMELIN
Firm: 003646 Firm Name: HESO ELECTRICAL INC
Firm Phone: 718-204-8568  Firm Address: 3418 NORTHERN BLVD, STE 4-5 LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $732.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   NIGHT CLUB
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRIAN GEFTER
Owner Business Name: SG HOSPITALITY GROUP LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  4W 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  225A
D. 3 Phase Over 225 AMPS  1  (1) 800A, (2) 400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    396  49    35    120  180     
Buildings Total 396  49    35       120     180      
Total Units : 780 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/23/2014 Notice: 1 - FIRST NOTICE 08/07/2017
Power Issued: 06/23/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355246
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/04/2017 08/07/2017 TUR V (100) (5)
INSPECTION COMMENTS: OBJECTIONS ISSUED, APPLICATION NEEDS TO BE REFILED FOR ADVISORY, 1ST LEVEL 1200, 2ND LEVEL 400 AND 800 AMP SWITCHES, ALL PANELS NOT LISTED THEY ARE FILLE IN WRONG COLUMNS AND NOT ACCOUNTED FOR ALSO ALL FEEDERS MISSING FOR SS AND PANELS HVAC 4U
 
(2) 02/06/2018 02/07/2018 TUR C R (10) (0)
INSPECTION COMMENTS: ALL OBJECTIONS REMOVED, THIS APP REMAINS FOR BRANCH WIRING (SEE DETAILS), ALL ADVISORY PORTION, PANELS AND ASSOCIATED FEEDERS, 10POINT METER , AND FA SWITCH 30A TO GO ON APP M00004860 THAT APP TO INCLUDE DIFFERENCE OF THIS APP

OBJECTION FOR APPLICATION #: M355246
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001)410. , 110.2 MATERIAL FOR HANGING EXIT SIGNS NOT APPROVED FLEXIBLECORD
RSLV 08/04/2017 08/04/2017 02/06/2018
 
002 (999) OTHER
(FLOOR: 001)110.2 PER SUPERVISOR NEED CUT SHEETS FOR ALL CUSTOM LIGHTING ANDMODIFIED LIGHTING UL LISTING
RSLV 08/04/2017 08/04/2017 02/06/2018
 
003 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR)110.2(B) ADVISORY BOARD PORTION NOT FILED 1200AMP SS 1ST LEVEL, 2NDLEVEL 400 AND 800 , AND FIRE ALARM 30AMP DISCONNECT ALL FEEDERSMISSING AND ALL PANELS AND HVAC NOT LISTED ALONG WITH WIRING
RSLV 08/04/2017 08/04/2017 02/06/2018
 
004 (999) OTHER
(CELLAR)110.26 ALL ELECTRICAL ROOMS 1200 AMPS AND OVER NEED PANIC DOORS
RSLV 08/04/2017 08/04/2017 02/06/2018
 
005 (999) OTHER
(GROUND FLOOR) GFCI NEEDED FOR SERVICE OUTLET BY AC EQUIPMENT 210.63
RSLV 08/04/2017 08/04/2017 02/06/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order