BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355133
Premises: 1120 5 AVENUE MANHATTAN BIN: 1047101     Block: 1505   Lot: 1
   
Application Completed and Certified

Filed: 1120 5 AV Census Tract:   160.01 Health Area:  2820
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 93 STREET,    EAST 94 STREET
Status:   C - JOB IS SIGNED OFF 10/30/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/19/2014 11:07 AM
Application Entered:   06/19/2014 Job Start Date:   06/19/2014
Last Change:   10/30/2014 Job End Date:   09/11/2015
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     09/26/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010102 Licensee Name: GEORGE HOLNESS
Firm: 002832 Firm Name: GEORGE HOLNESS
Firm Phone: 347-945-2512  Firm Address: 3870 WHITE PLAINS ROAD BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $52.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANDREW POSNER
Owner Business Name: BROWN HARRIS STEVENS
Authorized Representative:  ANDREW POSNER
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  CONTROLS

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001                     
Buildings Total                       
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/22/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING TO BOILER AND CONTROL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355133
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/15/2014 08/22/2014 PHG A (30) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 09/26/2014 10/03/2014 TOR C R (20) (0) Y
INSPECTION COMMENTS: PANEL EXISTING AND MOST EQUIPMENT

OBJECTION FOR APPLICATION #: M355133
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BMST EMT PIPE NOT SUPPORTED IN GAS RM
RSLV 08/15/2014 08/15/2014 09/26/2014
 
002 (999) OTHER
BSMT 7" NIPPLE IN POILER RM FROM TROUGH TO PANNEL TOO MANY WIPES 358.22
RSLV 08/15/2014 08/15/2014 09/26/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order