BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M355118
Premises: 180 HESTER STREET MANHATTAN BIN: 1087706     Block: 205   Lot: 7502
   
Application Completed and Certified

Filed: 180 HESTER ST Census Tract:   41 Health Area:  6800
1/FL Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   MOTT STREET,    MULBERRY STREET
Status:   C - JOB IS SIGNED OFF 11/14/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/19/2014 7:21 AM
Application Entered:   06/19/2014 Job Start Date:   06/19/2014
Last Change:   11/14/2014 Job End Date:   07/30/2014
Appointment Status:   
Last Inspection By:   RIVERA, F       On     11/05/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $153.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   STORE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT LEBENSFELD
Owner Business Name: 180 HESTER STREET INVESTO
Authorized Representative:  ROBERT LEBENSFELD
Relationship To Owner:   SELF


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    90  15    90             
Buildings Total 90  15    90                
Total Units : 202 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/27/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M355118
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/09/2014 09/15/2014 NRS A (65) (8) Y
INSPECTION COMMENTS: CORNER STORE INSIDE WIRING:LIGHT, RECEPTACLES, SEITCHES
 
(2) 10/20/2014 10/27/2014 NRS A Y (60) (1) Y
INSPECTION COMMENTS: ELECTRICIAN NO SHOW, ELECTRICIAN ASKED TENANT ENCLOSURES
 
(3) 11/05/2014 11/14/2014 FRI C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M355118
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
STORE MC E.G.C: INSULATION IN UNDER THE GROUND BAR SCREWS
RSLV 09/09/2014 10/20/2014 11/05/2014
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
STORE 6/3 MC FEEDER FOR PANEL USED AS 6/4 AC CABLE
RSLV 09/09/2014 10/20/2014 11/05/2014
 
003 (999) OTHER
STORE NO TIE BRAKER ON MOULTIWIRE CIRCUITS 110.4
RSLV 09/09/2014 10/20/2014 11/05/2014
 
004 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
STORE SWITCH BOX UNDER PANEL
RSLV 09/09/2014 09/09/2014 10/20/2014
 
005 (999) OTHER
STORE OUTLET BOXES AND PANEL SET TOO DEEP 314.20
RSLV 09/09/2014 10/20/2014 11/05/2014
 
006 ( 19) DEFECTIVE WIRING IS IN USE
STORE MC JUMPER BETWEEN 4' LED FIXTURES EXPOSED TO DAMAGE 9T-SHIRT AREA) 330.12
RSLV 09/09/2014 10/20/2014 11/05/2014
 
007 (999) OTHER
STORE NO SHOW WINDOW RECEPTACLES 210.62
RSLV 09/09/2014 10/20/2014 11/05/2014
 
008 (999) OTHER
STORE #6 AWG MC GROUND WIRE REIDENTIFIED TO USE AS NEUTRAL IN PANEL200.6
RSLV 09/09/2014 10/20/2014 11/05/2014
 
009 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1 FLOOR ZIPI SCREWS USED FOR PANEL COVER 110.(B)
RSLV 10/20/2014 10/20/2014 11/05/2014