| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
2 |
3-100A SWITCH |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
1-400A SWITCH |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
3 SET 0F # 2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1 SET OF 3/0 |
| D. Over 250 MCM |
1 |
1 SET 500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
MAIN BREAKER COMBO |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE T-OUT: OPEN BOXES FOR LIGHT. AM 110.2A |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 002 |
(999) |
OTHER SOUTH STORE: MAIN DISC DOUBLE LUG ON POWER. 110.14A,3B |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 003 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED SOUTH STORE: 100A MAIN CB UNDERSIZE WIRE. T.310.16 |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 004 |
(999) |
OTHER PLP: NO MAIN CB. 408.36F |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 005 |
(999) |
OTHER PLP: DOUBLE LUG ON POWER. 110.14A.3B |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BSMT: EL.RM. TAP FOR S,N STORE AND PLP FROM TAP OF 400A. 240.21 |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 007 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT: EL.RM. A/C CABLE NOT PROPERLY SECURED. 320.30 |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 008 |
( 19) |
DEFECTIVE WIRING IS IN USE EL.RM: OPEN WIRING. AM.110.2A |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 009 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY EL.RM: NO DIRECTORY IN PANELS. 408.4 |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |
| |
| 010 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) BSMT: EMT NOT PROPERLY SUPPORTED (END BOX TO S.S) 358.30 |
RSLV |
11/03/2014 |
11/03/2014 |
12/17/2014 |