NYC Department of Buildings
Electrical Application Details for App #: M354804
Premises: 28 AVENUE B MANHATTAN BIN: 1004975     Block: 398   Lot: 33
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 28 AV B Census Tract:   30.02 Health Area:  6600
BASEMENT AND ALL APARTMENTS Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
DOB Cross Street(s):   EAST 2 STREET,    EAST 3 STREET
Status:   C - JOB IS SIGNED OFF 08/08/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/11/2014 9:15 PM
Application Entered:   06/11/2014 Job Start Date:   06/11/2014
Last Change:   08/08/2018 Job End Date:   06/11/2015
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     11/27/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012276 Licensee Name: ORLANDO D TORRES
Firm: 004033 Firm Name: O.K. ELEC'L SERVICE CORP
Firm Phone: 718-652-1212  Firm Address: 727A BURKE AVENUE BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $824.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 16 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALAN WEINSTEIN
Owner Business Name: AVENUE B PROPERTY
Authorized Representative:  ALAN WEINSTEIN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1- 400 AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  17  3- #6 THHN, 4- #2 THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4- 250 MCM
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  16  1- 100 AMPS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1- 100 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2A  10             
002  2B  10             
002  2C  10             
002  2D  10             
003  3A  10             
003  3B  10             
003  3C  10             
003  3D  10             
004  4A  10             
004  4B  10             
004  4C  10             
004  4D  10             
005  5A  10             
005  5B  10             
005  5C  10             
005  5D  10             
Buildings Total 64  160  16  64  64                
Total Units : 368 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 16 #4-Wire 1 #10-Wire 0
Existing Meters 17 + New Meters 17 - Removed Meters 17 = Total Meters 17

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/11/2014 Notice: C - CALL TO OFFICE 05/30/2017
Power Issued: 06/11/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MAIN SERVICE EQUIPMENT AND GENERAL WIRING FOR 16 APARTMENTSAND PLP.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M354804
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/19/2016 10/21/2016 EDB V (125) (7)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(2) 03/10/2017 03/10/2017 MLF J Y (29) (0)
INSPECTION COMMENTS: SOME OBJECTIONS REMAIN
 
(3) 03/31/2017 04/01/2017 MBE J X (45) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT MAKE CORRECTIONS TO ALL APT'S. INSPECTOR ALLOWED CONTRACTOR TO MAKE SOME CORRECTION DURING TIME OF INSPECTION, THERE WHERE TO MANY APT'S THAT NEEDED CORRECTIONS. CONTRACTOR WANTED TO CREATE OTHER VIOLATIONS WHILE TRYING NOT TO CORRECT HIS OBJECTIONS. INSPECTOR DID NOT GAIN ACCESS TO ALL APT'S AT THE TIME OF INSPECTION.
 
(4) 05/30/2017 05/30/2017 EDB J X (50) (0) Y
INSPECTION COMMENTS: NO ACCESS TO APT. : # 5A, 4A, 4C, 4D, 3C, 3D AND 2B.
 
(5) 11/27/2017 11/28/2017 MLF C R (29) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED

OBJECTION FOR APPLICATION #: M354804
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (291) BATHROOM RECEPTACLE NOT PROPERLY LOCATED
(ALL FLOORS) NO GFCI BY SINK 210.52
RSLV 10/19/2016 10/19/2016 03/10/2017
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) PENINSULA MISSING GFCI 210.8,52
RSLV 10/19/2016 10/19/2016 03/10/2017
 
003 (999) OTHER
(ALL FLOORS) RECEPTACLE FROM WALL NOT PER. 314.20,21
RSLV 10/19/2016 10/19/2016 03/10/2017
 
004 (999) OTHER
(ALL FLOORS)PANELS: MULTIWIRE CKT. NO GROUPED NO SIMULT. DISC. 210.4
RSLV 10/19/2016 10/19/2016 11/27/2017
 
005 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(CELLAR)RACEWAY TO APT(S) : OVER 10 CURRENT CONDUCTORS T. 314.15B2A
RSLV 10/19/2016 10/19/2016 03/10/2017
 
006 (261) ELECTRICAL CLOSETS/SERVICE ROOM IS USED FOR OTHER PURPOSES
(CELLAR) EL. SERVICE ROOM USED FOR STORAGE 110.25
RSLV 10/19/2016 10/19/2016 03/10/2017
 
007 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(CELLAR) PLP PANEL 110.12
RSLV 10/19/2016 10/19/2016 03/10/2017