BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M354756
Premises: 303 EAST 10 STREET MANHATTAN BIN: 1076962     Block: 404   Lot: 54
   
Application Completed and Certified

Filed: 303 E 10 ST Census Tract:   34 Health Area:  6200
APT# 10 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
Special Place Name:   APT# 10
DOB Cross Street(s):   AVENUE A,    AVENUE B
Status:   C - JOB IS SIGNED OFF 03/10/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/11/2014 10:55 AM
Application Entered:   06/11/2014 Job Start Date:   06/16/2014
Last Change:   03/10/2015 Job End Date:   07/30/2014
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     02/23/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009860 Licensee Name: JOSEPH TODARO
Firm: 002632 Firm Name: TNT ELECTRIC CO., INC.
Firm Phone: 347-763-2342  Firm Address: 41 BOX STREET, STE 301 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $59.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ESTATE REALTY INC
Authorized Representative:  ROBERT GIURDANELLA
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  10  10             
Buildings Total 10                
Total Units : 28 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/03/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  APT. # 10

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M354756
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/29/2015 02/03/2015 DNM A (30) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 02/23/2015 02/27/2015 HMC C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M354756
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
T-OUT RECEPTACLES ARE NOT TAMPERPROOF THROUGHOUT (406.11)
RSLV 01/29/2015 01/29/2015 02/23/2015
 
002 (999) OTHER
A/C 11OV IS NOT ARE FAULT PROTECTED (210.12)
RSLV 01/29/2015 01/29/2015 02/23/2015
 
003 (999) OTHER
PANEL MULTIWIRE BRANCH CIRCUITS NOT ON SINGLOE TIE OR 2 POLE BREAKER(210.4D)
RSLV 01/29/2015 01/29/2015 02/23/2015
 
004 (999) OTHER
T-OUT A.F.C.I PROTECTION IS NOT PROVIDED FOR OUTLETS, LIGHTS
RSLV 01/29/2015 01/29/2015 02/23/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order