BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M354464
Premises: 547 BROADWAY MANHATTAN BIN: 1007577     Block: 498   Lot: 15
   
Application Completed and Certified

Filed: 547 BROADWAY Census Tract:   49 Health Area:  6800
SUB CELLAR, CELLAR, 1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   SPRING STREET,    PRINCE STREET
Status:   C - JOB IS SIGNED OFF 10/30/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/04/2014 8:50 AM
Application Entered:   06/04/2014 Job Start Date:   06/04/2014
Last Change:   10/30/2014 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     10/27/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011200 Licensee Name: CHRIS RICHEY
Firm: 002605 Firm Name: C.M. RICHEY ELEC'L CONTR
Firm Phone: 718-499-7417  Firm Address: 1001 SIXTH AVENUE SUITE 1102 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $318.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ABS PARTNERS
Authorized Representative:  DAVID GAROFALO
Relationship To Owner:   GENERAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  4 #3/0 1 #6
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  3 #10 1 #10G
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB    18      30         
CEL    106  15             
001    184  46         
Buildings Total 308  65         39         
Total Units : 422 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/21/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  303E33G01-JES PROVIDE POWER FOR (1) HANDICAP LIFT FEEDER ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M354464
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/04/2014 09/09/2014 EID V (50) (4) Y
INSPECTION COMMENTS: NOT INSPECTED: ALL GND FL & SUB CELLUAR BRANCH WIRING
 
(2) 10/06/2014 10/21/2014 NRS A Y (70) (7) Y
INSPECTION COMMENTS: NONE
 
(3) 10/27/2014 10/30/2014 EDB C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M354464
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
CELLAR 3/4" COND AT PANEL CONDUCTORS NEEDS TO BE DERATED
RSLV 09/04/2014 10/06/2014 10/27/2014
 
002 (999) OTHER
CELLAR MULT-WIRE BRANCH CKT NEED TO BE GROUPED/NO HANDLE TIES(210.4.B)
RSLV 09/04/2014 10/06/2014 10/27/2014
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
CELLAR PANEL NO DIRECTORY
RSLV 09/04/2014 10/06/2014 10/27/2014
 
004 (999) OTHER
DISC FOR LIFT NOT ACCESSIBLE (110.26)
RSLV 09/04/2014 09/04/2014 10/06/2014
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
CELLAR: EXISTING PANEL
RSLV 10/06/2014 10/06/2014 10/27/2014
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SUB: BOTH ELEVATOR RELATED 30A SWITCH
RSLV 10/06/2014 10/06/2014 10/27/2014
 
007 (999) OTHER
SUB: MACHINE ROOM SWITCH BOX. 404.9(A)
RSLV 10/06/2014 10/06/2014 10/27/2014
 
008 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
SUB: LIGHT FIXTURES
RSLV 10/06/2014 10/06/2014 10/27/2014
 
009 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SUB: LIGHT FIXTURES SHEET MATEL GR SCREW. 250.8
RSLV 10/06/2014 10/06/2014 10/27/2014
 
010 (999) OTHER
BASE: A/C NOT FUSED AS PER NAME PLATE.ALL 3. 440.22(C)
RSLV 10/06/2014 10/06/2014 10/27/2014
 
011 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
GROUND: FOR LIGHT FIXTURES
RSLV 10/06/2014 10/06/2014 10/27/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.