| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
4 #3/0 1 #6 |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
3 #10 1 #10G |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED CELLAR 3/4" COND AT PANEL CONDUCTORS NEEDS TO BE DERATED |
RSLV |
09/04/2014 |
10/06/2014 |
10/27/2014 |
| |
| 002 |
(999) |
OTHER CELLAR MULT-WIRE BRANCH CKT NEED TO BE GROUPED/NO HANDLE TIES(210.4.B) |
RSLV |
09/04/2014 |
10/06/2014 |
10/27/2014 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY CELLAR PANEL NO DIRECTORY |
RSLV |
09/04/2014 |
10/06/2014 |
10/27/2014 |
| |
| 004 |
(999) |
OTHER DISC FOR LIFT NOT ACCESSIBLE (110.26) |
RSLV |
09/04/2014 |
09/04/2014 |
10/06/2014 |
| |
| 005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX CELLAR: EXISTING PANEL |
RSLV |
10/06/2014 |
10/06/2014 |
10/27/2014 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED SUB: BOTH ELEVATOR RELATED 30A SWITCH |
RSLV |
10/06/2014 |
10/06/2014 |
10/27/2014 |
| |
| 007 |
(999) |
OTHER SUB: MACHINE ROOM SWITCH BOX. 404.9(A) |
RSLV |
10/06/2014 |
10/06/2014 |
10/27/2014 |
| |
| 008 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX SUB: LIGHT FIXTURES |
RSLV |
10/06/2014 |
10/06/2014 |
10/27/2014 |
| |
| 009 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED SUB: LIGHT FIXTURES SHEET MATEL GR SCREW. 250.8 |
RSLV |
10/06/2014 |
10/06/2014 |
10/27/2014 |
| |
| 010 |
(999) |
OTHER BASE: A/C NOT FUSED AS PER NAME PLATE.ALL 3. 440.22(C) |
RSLV |
10/06/2014 |
10/06/2014 |
10/27/2014 |
| |
| 011 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD GROUND: FOR LIGHT FIXTURES |
RSLV |
10/06/2014 |
10/06/2014 |
10/27/2014 |