Electrical Application Details for App #: M354341
Premises: 148 BROADWAY MANHATTAN BIN: 1001087     Block: 64   Lot: 12
   

Filed: 150 BROADWAY Census Tract:   15.02
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   LIBERTY STREET,    CORTLANDT STREET
Status:   K - CLOSED/CANCELLED 09/22/2014
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/02/2014 Job Start Date:   05/08/2014
Last Change:   09/22/2014 Job End Date:   09/01/2014
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     09/16/2014      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011831 Licensee Name: JAMES T GIORGIO, JR
Firm: 002393 Firm Name: B & G ELECL CONTR OF NY I
Firm Phone: 718-925-6900  Firm Address: 38-22 55 STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $0.00
Hurricane Sandy Damage:   Yes
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   51818     Submittal #: 13A0282  
Owner / Occup:
Owner Business Name: 150 BROADWAY ASSOC LP
Authorized Representative:  DANIEL MISHAEL
Relationship To Owner:   PROP MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1-2500 1-2000.1-1200
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  15  15-4#600KCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  1-2500A DB
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 3
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/02/2014 Notice: 1 - FIRST NOTICE 07/28/2014
Power Issued: 06/02/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB#4549 HURRICANE SANDY SWITCH GEAR REPLACEMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M354341
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/09/2014 07/28/2014 LBI V G (160) (4) Y
INSPECTION COMMENTS: V
 
(2) 09/16/2014 09/22/2014 LBI K R G (30) (0) Y
INSPECTION COMMENTS: SEE M356576

OBJECTION FOR APPLICATION #: M354341
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
BASEMENT 1200 DISTRIBUTION BOARD COPPER BUSS AND FUSES ( AM 110.2B)
RSLV 07/09/2014 07/09/2014 09/16/2014
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT FA CUTOUT SVC REACEWAY NOT BONDED AT WIREWAY 250.92
RSLV 07/09/2014 07/09/2014 09/16/2014
 
003 (999) OTHER
BASEMENT GEC REACEWAY NOT PROPERLY MADE CONTINOUS AT ROD AND WATER MAIN 250.64E
RSLV 07/09/2014 07/09/2014 09/16/2014
 
004 (999) OTHER
BASEMENT DEFECTIVE GROUND CLAMP IN USE AT WATER MAIN 250.68B
RSLV 07/09/2014 07/09/2014 09/16/2014