| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(228) |
USING PANEL AS A RACEWAY (FLOOR: 009)312.8/ FEEDER INSTALLED, AT METER ENCLOSURE USED AS RACEWAY. |
OPEN |
02/04/2025 |
02/04/2025 |
|
| |
| 002 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 009) 406.4, DIRECTORY NOT PROVIDED AT 100 AMP PANEL. |
OPEN |
02/04/2025 |
02/04/2025 |
|
| |
| 003 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (FLOOR: 009)3/4" 1" 11/2"- EMT CONDUIT IS NOT PROPERLY SUPPORTED 358.30, ATHALLWAY. |
OPEN |
02/04/2025 |
02/04/2025 |
|
| |
| 004 |
(999) |
OTHER (FLOOR: 009)CONTRACTOR TO ADD, FLR DESCRIPTION, 9 FLR, 4-100 AMP DIS SWITCHES,TOTAL 4 INSTALLED,- 4-4 WIRE METER, TOTAL 4 INSTALLED./ MISSING FROMOLD APPS M354301. |
OPEN |
02/04/2025 |
02/04/2025 |
|