Electrical Application Details for App #: M354237
Premises: 505 8 AVENUE MANHATTAN BIN: 1013575     Block: 759   Lot: 37
   
Application Completed and Certified

Filed: 505 8 AV Census Tract:   111 Health Area:  5500
SUITE 12A Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
DOB Cross Street(s):   WEST 35 STREET,    WEST 36 STREET
Status:   C - JOB IS SIGNED OFF 09/24/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2014 11:57 AM
Application Entered:   05/29/2014 Job Start Date:   05/30/2014
Last Change:   09/24/2014 Job End Date:   05/30/2015
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     09/18/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011252 Licensee Name: ALBERT DATTOLO
Firm: 001211 Firm Name: RAINBOW ELECTRIC CO., INC
Firm Phone: 718-521-0926  Firm Address: 76-18 ROCKAWAY BLVD WOODHAVEN NY 11421 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $67.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: WHITESTAR CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
012  12A  30  50    10  30             
Buildings Total 30  50    10  30                
Total Units : 120 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/20/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ALL NEW EXCEPT FEEDER AND PANEL. NEW LIGHTS, OUTLETS, SWITCHES. NO FIRE ALARM WORK.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M354237
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/14/2014 08/20/2014 DNM A (30) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 09/18/2014 09/24/2014 EDB C R (40) (0) Y
INSPECTION COMMENTS: STE#12A03

OBJECTION FOR APPLICATION #: M354237
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANEL: MULTIWIRE BRANCH CIRCUIT NOT ON SINGLE TIE OR 2 POLE BREAKER210.4
RSLV 08/14/2014 08/14/2014 09/18/2014
 
002 (999) OTHER
PANEL: SUFFICIENT WORK SPACE NOT PROVIDED PANEL HAS NO CLEARANCE OFAT LEAST 3' 110.26
RSLV 08/14/2014 08/14/2014 09/18/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.