BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M353115
Premises: 35 COOPER SQUARE MANHATTAN BIN: 1090311     Block: 461   Lot: 8
   
Application Completed and Certified

Filed: 200 E 6 ST Census Tract:   38
N/A Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
Related Job Number:    121325413
DOB Cross Street(s):   COOPER SQUARE,    TARAS SHEVCHENKO PLACE
Status:   C - JOB IS SIGNED OFF 09/14/2015
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   04/28/2014 Job Start Date:   03/26/2014
Last Change:   09/14/2015 Job End Date:   06/30/2015
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     08/31/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011200 Licensee Name: CHRIS RICHEY
Firm: 002605 Firm Name: C.M. RICHEY ELEC'L CONTR
Firm Phone: 718-499-7417  Firm Address: 1001 SIXTH AVENUE SUITE 1102 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $4,880.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121325413
Building Used As:   Z - Other
Store / Other:   DORMITORY
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52096     Submittal #: 13A0711  
Owner / Occup: ARUN BHATIA
Owner Business Name: COOPER & 6TH PROPERTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  (1) 100AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  (1) 600AMP
D. 601 Up to 1200 AMPS  1  (1) 1200AMP
E. Over 1200 AMPS  1  (1) 400AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  1  (1) #2
C. Over 1/0 to 250 MCM  6  
D. Over 250 MCM  17  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  31  (1) 60,(5) 100,(25) 225
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB    92  52    18    11     
CEL    53  29    24    15  11     
001    90  20      200  10     
002    61  61  14  28        17  39     
003    67  122  14  30        14  18     
004    67  122  14  30        14  18     
005    67  122  14  30        14  18     
006    63  139  14  28        14  20     
007    59  58  16        12     
008    46  91  22        10  13     
009    46  91  22        10  13     
010    46  91  22        10  13     
011    46  91  22        10  13     
012    46  91  22        10  13     
ROF    12  10        18  118  19     
Buildings Total 861  1190  121  322       335     231      
Total Units : 3060 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 4 #10-Wire 0
Existing Meters 0 + New Meters 7 - Removed Meters 0 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/28/2014 Notice: 1 - FIRST NOTICE 06/29/2015
Power Issued: 04/28/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M353115
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/04/2015 06/09/2015 EID Z (0) (0) Y
INSPECTION COMMENTS: CANCELLED BY OFFICE
 
(2) 06/22/2015 06/29/2015 GYM A E (210) (10) Y
INSPECTION COMMENTS: SEE APPLICATION #M357908,29 SETS FEEDERS SERVICE EMT CONDUCTORS
 
(3) 07/28/2015 08/03/2015 CBK J Y E (100) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 08/04/2015 08/11/2015 GYM Z (0) (0) Y
INSPECTION COMMENTS: CANCELLED
 
(5) 08/31/2015 09/03/2015 EID C R E (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M353115
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: LIMITED SERVICE FIRE PUMP SUPPLY CONDUCTORS SHALL BE INSTALLEDIN RIGID METAL CONDUIT.. SECTION 695.6
RSLV 06/22/2015 06/22/2015 07/28/2015
 
002 (999) OTHER
A) B SMT??: 600 AMP DIS.SW.NEUTRAL BOND NOT REQUIRED.. 250.24
RSLV 06/22/2015 06/22/2015 07/28/2015
 
003 (999) OTHER
B) FIRE PUMP FEEDER FROM CONTROLLER NOT INSTALLED.. ART.695.6
RSLV 06/22/2015 06/22/2015 07/28/2015
 
004 (999) OTHER
C) BSMT: 3 AM SER E.M.T NOT BONDED.. ART.250.92
RSLV 06/22/2015 06/22/2015 07/28/2015
 
005 (999) OTHER
D) ALL REQ'D RECEPTACLES LISTED TAMPER RESISTANT: ART.406.11
RSLV 06/22/2015 07/28/2015 08/31/2015
 
006 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
ALL FLS: RECEPTS THROUGH-OUT
RSLV 06/22/2015 06/22/2015 07/28/2015
 
007 (999) OTHER
E) BSMT: FIRE PUMP SERVICE DISCONNECTION SHALL BE MARKED DO NOT DIS-CONNECTT.. ART.695.4
RSLV 06/22/2015 06/22/2015 07/28/2015
 
008 (999) OTHER
F) BSMT: NO PANIC HARDWARE PROVIDED DOORS.. ART.110.26
RSLV 06/22/2015 06/22/2015 07/28/2015
 
009 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTDOOR: ARMORED CABLES
RSLV 06/22/2015 06/22/2015 07/28/2015
 
010 (999) OTHER
G) ROOF: PANEL DOOR MUST BE OPENABLE TO AT LEAST 90*.. 110.26(HDPR)
RSLV 06/22/2015 06/22/2015 07/28/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.