| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
(1) 100AMP |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
(1) 600AMP |
| D. 601 Up to 1200 AMPS |
1 |
(1) 1200AMP |
| E. Over 1200 AMPS |
1 |
(1) 400AMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
6 |
|
| B. Over #2 to 1/0 |
1 |
(1) #2 |
| C. Over 1/0 to 250 MCM |
6 |
|
| D. Over 250 MCM |
17 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
31 |
(1) 60,(5) 100,(25) 225 |
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: LIMITED SERVICE FIRE PUMP SUPPLY CONDUCTORS SHALL BE INSTALLEDIN RIGID METAL CONDUIT.. SECTION 695.6 |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 002 |
(999) |
OTHER A) B SMT??: 600 AMP DIS.SW.NEUTRAL BOND NOT REQUIRED.. 250.24 |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 003 |
(999) |
OTHER B) FIRE PUMP FEEDER FROM CONTROLLER NOT INSTALLED.. ART.695.6 |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 004 |
(999) |
OTHER C) BSMT: 3 AM SER E.M.T NOT BONDED.. ART.250.92 |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 005 |
(999) |
OTHER D) ALL REQ'D RECEPTACLES LISTED TAMPER RESISTANT: ART.406.11 |
RSLV |
06/22/2015 |
07/28/2015 |
08/31/2015 |
| |
| 006 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER ALL FLS: RECEPTS THROUGH-OUT |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 007 |
(999) |
OTHER E) BSMT: FIRE PUMP SERVICE DISCONNECTION SHALL BE MARKED DO NOT DIS-CONNECTT.. ART.695.4 |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 008 |
(999) |
OTHER F) BSMT: NO PANIC HARDWARE PROVIDED DOORS.. ART.110.26 |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 009 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED OUTDOOR: ARMORED CABLES |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |
| |
| 010 |
(999) |
OTHER G) ROOF: PANEL DOOR MUST BE OPENABLE TO AT LEAST 90*.. 110.26(HDPR) |
RSLV |
06/22/2015 |
06/22/2015 |
07/28/2015 |