| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
100A |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
3/3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS 7NW WIRES TAPPED MORE THAN ONCE 240.21 |
OPEN |
09/29/2015 |
09/29/2015 |
|
| |
| 002 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ALL FLOORS) 7NW EMT NOT SUPPORTED 358.30 |
RSLV |
09/29/2015 |
09/29/2015 |
03/08/2016 |
| |
| 003 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (ALL FLOORS) 7NW: KO SEALS NOT SEALED IN DISCONNECT 110.12 |
RSLV |
09/29/2015 |
09/29/2015 |
03/08/2016 |
| |
| 004 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (ALL FLOORS) 7NW: BUSHING MISSING ON PIPE TO SWITCH + RISER 300.46 |
RSLV |
09/29/2015 |
09/29/2015 |
03/08/2016 |
| |
| 005 |
(999) |
OTHER (FLOOR: 007)110.3, 110.21,110.22, PERMANENT MARKING AND ID FOR PANEL DISCONNECTAND METER. ALL MUST BE LABELED AS PER CODE |
OPEN |
03/08/2016 |
03/08/2016 |
|
| |
| 006 |
(999) |
OTHER (FLOOR: 007)110.14 TAP FOR METER AND PANEL ON BUG NUT WITH TOTAL 4 WIRES SPLITBOLT IS FOR TWO WIRES MUST CHANGE |
OPEN |
03/08/2016 |
03/08/2016 |
|
| |
| 007 |
(999) |
OTHER (FLOOR: 007) 110.25 ELECTRIC CLOSET NO STORAGE |
OPEN |
03/08/2016 |
03/08/2016 |
|