BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M352915
Premises: 236 WEST 26 STREET MANHATTAN BIN: 1014205     Block: 775   Lot: 60
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 236 W 26 ST Census Tract:   91 Health Area:  5200
APT 7NW Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/23/2014 9:49 PM
Application Entered:   04/23/2014 Job Start Date:   04/24/2014
Last Change:   09/29/2025 Job End Date:   09/23/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     03/08/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  Y - PARTLY REMOVED

License #: 012423 Licensee Name: TOMASZ PUZA
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
010587 FRENKEL, HARRY 002697 APOLLO ELECTRIC INC.

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $63.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALEX CHERTORISKY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3/3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 0 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 04/23/2014 Notice: 1 - FIRST NOTICE 03/09/2016
Power Issued: 04/23/2014 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M352915
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/29/2015 10/01/2015 EDB A E (40) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 03/08/2016 03/09/2016 TUR V Y (40) (3)
INSPECTION COMMENTS: PART OBJECTIONS REMOVED, OBJECTIONS ADDED NOT FINAL OBJECTIONS EXIST

OBJECTION FOR APPLICATION #: M352915
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
7NW WIRES TAPPED MORE THAN ONCE 240.21
OPEN 09/29/2015 09/29/2015
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) 7NW EMT NOT SUPPORTED 358.30
RSLV 09/29/2015 09/29/2015 03/08/2016
 
003 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ALL FLOORS) 7NW: KO SEALS NOT SEALED IN DISCONNECT 110.12
RSLV 09/29/2015 09/29/2015 03/08/2016
 
004 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ALL FLOORS) 7NW: BUSHING MISSING ON PIPE TO SWITCH + RISER 300.46
RSLV 09/29/2015 09/29/2015 03/08/2016
 
005 (999) OTHER
(FLOOR: 007)110.3, 110.21,110.22, PERMANENT MARKING AND ID FOR PANEL DISCONNECTAND METER. ALL MUST BE LABELED AS PER CODE
OPEN 03/08/2016 03/08/2016
 
006 (999) OTHER
(FLOOR: 007)110.14 TAP FOR METER AND PANEL ON BUG NUT WITH TOTAL 4 WIRES SPLITBOLT IS FOR TWO WIRES MUST CHANGE
OPEN 03/08/2016 03/08/2016
 
007 (999) OTHER
(FLOOR: 007) 110.25 ELECTRIC CLOSET NO STORAGE
OPEN 03/08/2016 03/08/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.