BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M352892
Premises: 83 BAXTER STREET MANHATTAN BIN: 1002368     Block: 199   Lot: 3
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 83 BAXTER ST Census Tract:   29 Health Area:  7700
NEAR CANAL STREET Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   103
DOB Cross Street(s):   WHITE STREET,    WALKER STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/23/2014 11:58 AM
Application Entered:   04/23/2014 Job Start Date:   04/23/2014
Last Change:   08/22/2025 Job End Date:   04/29/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     11/19/2015      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011016 Licensee Name: EGBERT BAPTISTE
Firm: 002355 Firm Name: REM & SONS LIC ELEC CONT
Firm Phone: 718-434-5521  Firm Address: 583 NOSTRAND AVENUE CORP BROOKLYN NY 11216 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $160.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (3  Stores, 38 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: OWNER OWNER
Owner Business Name: MAROLDA PROPERTIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  6/3 RISERS
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008                       
Buildings Total                       
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 38 #4-Wire 4 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 04/23/2014 Notice: 1 - FIRST NOTICE 12/03/2015
Power Issued: 04/23/2014 Response:  

Follow-Up:
Contractor's Comments:  CORRECTING VIOLATION # M275212

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M352892
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/23/2014 06/04/2014 TOR P (45) (0) Y
INSPECTION COMMENTS: NO ACCESS TO APT IS SEE APPS M 352532 M352649
 
(2) 11/19/2015 12/03/2015 BUR A E (30) (2) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M352892
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CELLAR #8 AWG NOT PROPERLY PROTECTED ON 60 AMP FUSE. 240.4
OPEN 11/19/2015 11/19/2015
 
002 (999) OTHER
CELLAR EMT CONDUIT NOT SUPPORTED PROPERLY 358.30
OPEN 11/19/2015 11/19/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.