BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M352857
Premises: 505 EAST 89 STREET MANHATTAN BIN: 1051369     Block: 1586   Lot: 5
   
Application Completed and Certified

Filed: 515 E 89 ST Census Tract:   152 Health Area:  3300
6A Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   YORK AVENUE,    EAST END AVENUE
Status:   C - JOB IS SIGNED OFF 03/06/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/22/2014 6:49 PM
Application Entered:   04/22/2014 Job Start Date:   04/22/2014
Last Change:   03/06/2015 Job End Date:   04/22/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     02/27/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012244 Licensee Name: JEAN PAUL WILLIAMS
Firm: 003639 Firm Name: GOLD STAR ELECT'L, INC
Firm Phone: 718-961-7827  Firm Address: 59-24 57TH STREET MASPETH NY 11378 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
012012 MOUNAS, SAMY A 003639 GOLD STAR ELECT'L, INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $280.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: L KAYE
Owner Business Name: KAYE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  THREE 3/0
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  THREE 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  42 CKT AND 24 CKT PANELS
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  A/D  103  93  49  103  19         
Buildings Total 103  93  49  103     19           
Total Units : 370 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/22/2014 Notice: 1 - FIRST NOTICE 02/13/2015
Power Issued: 04/22/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REWIRE APARTMENTS 6A AND 6D

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M352857
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/16/2014 12/22/2014 UMS J E (35) (0) Y
INSPECTION COMMENTS: NOT READY FOR INSPECTION. LOOSE WIRES ALL OVER APARTMENT
 
(2) 01/12/2015 01/16/2015 PHG N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 02/10/2015 02/13/2015 PHG V E (60) (4) Y
INSPECTION COMMENTS: DID NOT SEE OUTSIDE WORK OR A/C WORK
 
(4) 02/27/2015 03/06/2015 PHG C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M352857
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
WATER GROUND NOT CONTINOUS 250.69
RSLV 02/10/2015 02/10/2015 02/27/2015
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
AFCI NOT PROVIDED IN ALL 2 FT 210.12
RSLV 02/10/2015 02/10/2015 02/27/2015
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
AFCI NOT PROVIDED IN 1FLOOR A/V CLOSET 210.12
RSLV 02/10/2015 02/10/2015 02/27/2015
 
004 (999) OTHER
ALL PUCK LIGHTS HAVE FLEX CORD BEHIND
RSLV 02/10/2015 02/10/2015 02/27/2015