BIS Menu  |  Elevators  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M352501
Premises: 12 EAST 13 STREET MANHATTAN BIN: 1009378     Block: 570   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 12 E 13 ST Census Tract:   61 Health Area:  5700
5 AVENUE & UNIVERSITY PLACE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 05/26/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/11/2014 12:26 PM
Application Entered:   04/11/2014 Job Start Date:   04/11/2014
Last Change:   05/26/2016 Job End Date:   07/02/2016
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     04/07/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010118 Licensee Name: ROBERT MARCHISOTTO
Firm: 002914 Firm Name: R.C.M. ELECTRIC CORP.
Firm Phone: 718-339-2680  Firm Address: 1915 MCDONALD AVE. BLDG REAR BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $373.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   G - Garage
Special Cert Approval:   L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSH SCHUSTER
Owner Business Name: 12 EAST 13 STREET LLC
Authorized Representative:  JOSH SCHUSTER
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  1  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 03/21/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M352501
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/04/2015 09/11/2015 PHG V (30) (3) Y
INSPECTION COMMENTS: DID NOT SEE BOTH MOTORS AND TOP OF CAR FOR 1P48035;CAR LIGHTS ON 12FL NO LOAD
 
(2) 03/18/2016 03/21/2016 GYM H X (35) (0) Y
INSPECTION COMMENTS: NO ACCESS TO ELEVATOR PITS
 
(3) 04/07/2016 04/11/2016 GYM C R (40) (0)
INSPECTION COMMENTS: ID # 1P48035 1P48606

OBJECTION FOR APPLICATION #: M352501
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) BSMT: EMT IN BSMT MOTOR RM NOT SUPPORTED
RSLV 09/04/2015 09/04/2015 04/07/2016
 
002 (999) OTHER
(ALL FLOORS) 12FL: NO WORKING SPACE FOR 12FL SW IN MOTOR RM.. 110.26
RSLV 09/04/2015 09/04/2015 04/07/2016
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) 12FL: NO GRND IN FMC FOR ELECTRIC SW FEED.. 250.118
RSLV 09/04/2015 09/04/2015 04/07/2016