BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M352425
Premises: 185 AVENUE B MANHATTAN BIN: 1089953     Block: 394   Lot: 10
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 189 AV B Census Tract:   28 Health Area:  6300
CELLAR THRU 6 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
Related Job Number:    120818909
DOB Cross Street(s):   EAST 11 STREET,    EAST 12 STREET
Status:   C - JOB IS SIGNED OFF 07/18/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/09/2014 10:43 PM
Application Entered:   04/09/2014 Job Start Date:   04/10/2014
Last Change:   07/18/2017 Job End Date:   12/31/2016
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     05/04/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012068 Licensee Name: RICHARD A RAINEY
Firm: 003763 Firm Name: HUNTER ELECTRICAL SER CP
Firm Phone: 718-729-0010  Firm Address: 4528 VERNON BLVD CORP LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $2,686.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  120818909
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: HUBB REALTY
Authorized Representative:  STEVE GANGI
Relationship To Owner:   SUPERVISOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  150A
C. 201 Up to 600 AMPS  4  600A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  40  FEEDERS TO APARTMENTS
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  44  100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    120  82    20    20         
001    108  82    21           
002    119  124    37           
003    119  124    37           
004    119  124    37           
005    119  124    37           
006    68  124    37           
ROF    10                 
Buildings Total 782  788    229       36           
Total Units : 1835 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 42 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/09/2014 Notice: 1 - FIRST NOTICE 04/03/2017
Power Issued: 04/09/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M352425
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/28/2016 06/28/2016 EDB J (50) (0) Y
INSPECTION COMMENTS: JOB 70% FINISH. CONTRACTOR NOT READY FOR INSPECTION. CONTRACTOR INSTALLED 2 X 600 A, ONE 800 A, ONE 1200 A F/P (40 HP),ONE 400 A AND 2 X 30 A F/A SERVICE SWITCHES .
 
(2) 07/28/2016 07/29/2016 TOR V (60) (6)
INSPECTION COMMENTS: SERVICE, FIRE PUMP AND CELLAR INSPECTED ONLY.
 
(3) 08/12/2016 08/16/2016 BUR J X (75) (0) Y
INSPECTION COMMENTS: ALL APARTMENTS INSPECTED, APPLICATION NEED TO BE AMENDED FOR ADDITIONAL FEEDERS AND PANELS, FEEDERS FOR APARTMENTS ADDED TO APPLICATION
 
(4) 09/22/2016 09/26/2016 STP V Y (30) (1)
INSPECTION COMMENTS: FAIL. NEED PAPERWORK ON FIRE RATED ROCK USED. VIOLATIONS PARTIALLY REMOVED.
 
(5) 12/27/2016 12/28/2016 STP J Y (30) (0)
INSPECTION COMMENTS: FAIL. DRAWING NEEDS DOB APPROVAL.
 
(6) 04/03/2017 04/03/2017 TSO V Y (1) (1)
INSPECTION COMMENTS: MADE FP OBJ CERTIFIABLE SO CUSTOMER CAN UPLOAD DOCS.
 
(7) 05/04/2017 05/04/2017 TOR C R (15) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M352425
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(CELLAR) FEEDERS FOR FIRE PUMP PASSING HALLWAY NEED TO BE FIRE RATED
RSLV 07/28/2016 07/28/2016 04/03/2017
 
002 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
(CELLAR) AIR HANDLERS T-OUT
RSLV 07/28/2016 07/28/2016 09/22/2016
 
003 (286) NO GFCI IN COMMERCIAL KITCHEN
(CELLAR) T-OUT
RSLV 07/28/2016 07/28/2016 09/22/2016
 
004 (999) OTHER
(CELLAR) NO SIGN ELECTRICAL ROOM 110.26 C 2
RSLV 07/28/2016 07/28/2016 12/27/2016
 
005 (999) OTHER
(CELLAR) NO SIGN FIRE PUMP DISCONNECT AT SERVICE SWICH 695
RSLV 07/28/2016 07/28/2016 12/27/2016
 
006 (999) OTHER
(CELLAR) FIXTURE NOT SUPPORTED T-OUT 410.30
RSLV 07/28/2016 07/28/2016 09/22/2016
 
007 (999) OTHER
(CELLAR) LP-CH-C MILLS CUT OFF 4/0 WIRE
RSLV 09/22/2016 09/22/2016 05/04/2017
 
008 (999) OTHER
(CELLAR) CONDUCTORS FOR FIRE PUMP NOT IN RATED ENCLOSURE.
RSLV 04/03/2017 04/03/2017 05/04/2017