| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
150A |
| C. 201 Up to 600 AMPS |
4 |
600A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
40 |
FEEDERS TO APARTMENTS |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
6 |
350MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
44 |
100A |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
06/28/2016 |
06/28/2016 |
EDB |
J |
|
|
(50) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
JOB 70% FINISH. CONTRACTOR NOT READY FOR INSPECTION. CONTRACTOR INSTALLED 2 X 600 A, ONE 800 A, ONE 1200 A F/P (40 HP),ONE 400 A AND 2 X 30 A F/A SERVICE SWITCHES .
|
| |
| (2) |
07/28/2016 |
07/29/2016 |
TOR |
V |
|
|
(60) |
|
(6) |
|
| INSPECTION COMMENTS:
|
SERVICE, FIRE PUMP AND CELLAR INSPECTED ONLY.
|
| |
| (3) |
08/12/2016 |
08/16/2016 |
BUR |
J |
X |
|
(75) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
ALL APARTMENTS INSPECTED, APPLICATION NEED TO BE AMENDED FOR ADDITIONAL FEEDERS AND PANELS, FEEDERS FOR APARTMENTS ADDED TO APPLICATION
|
| |
| (4) |
09/22/2016 |
09/26/2016 |
STP |
V |
Y |
|
(30) |
|
(1) |
|
| INSPECTION COMMENTS:
|
FAIL. NEED PAPERWORK ON FIRE RATED ROCK USED. VIOLATIONS PARTIALLY REMOVED.
|
| |
| (5) |
12/27/2016 |
12/28/2016 |
STP |
J |
Y |
|
(30) |
|
(0) |
|
| INSPECTION COMMENTS:
|
FAIL. DRAWING NEEDS DOB APPROVAL.
|
| |
| (6) |
04/03/2017 |
04/03/2017 |
TSO |
V |
Y |
|
(1) |
|
(1) |
|
| INSPECTION COMMENTS:
|
MADE FP OBJ CERTIFIABLE SO CUSTOMER CAN UPLOAD DOCS.
|
| |
| (7) |
05/04/2017 |
05/04/2017 |
TOR |
C |
R |
|
(15) |
|
(0) |
|
| INSPECTION COMMENTS:
|
PASS
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED (CELLAR) FEEDERS FOR FIRE PUMP PASSING HALLWAY NEED TO BE FIRE RATED |
RSLV |
07/28/2016 |
07/28/2016 |
04/03/2017 |
| |
| 002 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (CELLAR) AIR HANDLERS T-OUT |
RSLV |
07/28/2016 |
07/28/2016 |
09/22/2016 |
| |
| 003 |
(286) |
NO GFCI IN COMMERCIAL KITCHEN (CELLAR) T-OUT |
RSLV |
07/28/2016 |
07/28/2016 |
09/22/2016 |
| |
| 004 |
(999) |
OTHER (CELLAR) NO SIGN ELECTRICAL ROOM 110.26 C 2 |
RSLV |
07/28/2016 |
07/28/2016 |
12/27/2016 |
| |
| 005 |
(999) |
OTHER (CELLAR) NO SIGN FIRE PUMP DISCONNECT AT SERVICE SWICH 695 |
RSLV |
07/28/2016 |
07/28/2016 |
12/27/2016 |
| |
| 006 |
(999) |
OTHER (CELLAR) FIXTURE NOT SUPPORTED T-OUT 410.30 |
RSLV |
07/28/2016 |
07/28/2016 |
09/22/2016 |
| |
| 007 |
(999) |
OTHER (CELLAR) LP-CH-C MILLS CUT OFF 4/0 WIRE |
RSLV |
09/22/2016 |
09/22/2016 |
05/04/2017 |
| |
| 008 |
(999) |
OTHER (CELLAR) CONDUCTORS FOR FIRE PUMP NOT IN RATED ENCLOSURE. |
RSLV |
04/03/2017 |
04/03/2017 |
05/04/2017 |