Premises: 522 1 AVENUE MANHATTAN BIN: 1087297     Block: 962   Lot: 80
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 522 FIRST AV Census Tract:   62
PENTHOUSE #1 Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   NYU LANGONE MEDICAL CENTER
DOB Cross Street(s):   EAST 30 STREET,    EAST 33 STREET
Status:   C - JOB IS SIGNED OFF 08/27/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   03/28/2014 Job Start Date:   03/27/2014
Last Change:   08/27/2018 Job End Date:   04/18/2014
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     08/27/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 011240 Licensee Name: CRAIG GILSTON
Firm: 000591 Firm Name: GILSTON ELEC'L CONTNG LLC
Firm Phone: 212-410-7800  Firm Address: 338 EAST 95TH STREET NEW YORK NY 10128 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $940.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52193     Submittal #: 14A0037  
Owner / Occup:
Owner Business Name: NYU LANGONE MEDICAL CTR
Authorized Representative:  RICHARD COHEN
Relationship To Owner:   V.P. FACILITIES


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  2  1-800AMP 1-1200AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  6-4#500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB#1105 SMILOW SWITCHGEAR REPLACEMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M351962
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/27/2018 08/27/2018 CBK C (150) (0) Y
INSPECTION COMMENTS: CONTRACTOR REPLACES A 4000A DISTRIBUTION BOARD, AND CHANGE 1 4000A FUSE IN SERVICE SWITCH. 800A BUCKET WITH 800A A4BQ FUSE, AS SPARE.