Electrical Application Details for App #: M351894
Premises: 7 LAIGHT STREET MANHATTAN BIN: 1002736     Block: 212   Lot: 7503
   
Application Completed and Certified

Filed: 1 YORK ST Census Tract:   33 Health Area:  7700
11TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   AVENUE OF THE AMERICAS,    LAIGHT STREET
Status:   C - JOB IS SIGNED OFF 07/08/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/27/2014 9:53 AM
Application Entered:   03/27/2014 Job Start Date:   03/31/2014
Last Change:   07/08/2015 Job End Date:   03/31/2015
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     07/01/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010341 Licensee Name: WARREN OSTROFF
Firm: 002946 Firm Name: WARREN OSTROFF ELEC., INC
Firm Phone: 718-323-5200  Firm Address: 401 PARK AVENUE S. STE 861 NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $234.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: LANDRY'S
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  100.00
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011    79  120    35  136  16         
Buildings Total 79  120    35  136     16           
Total Units : 386 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/28/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M351894
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/24/2015 03/31/2015 DNM Z (0) (0) Y
INSPECTION COMMENTS: CANCELED WITH OFFICE
 
(2) 04/10/2015 04/22/2015 BUR V (65) (3) Y
INSPECTION COMMENTS: PANELS AND KITCHEN INSPECTED
 
(3) 04/24/2015 04/30/2015 LUF Z (0) (0) Y
INSPECTION COMMENTS: CANCELED WITH OFFICE
 
(4) 05/19/2015 05/28/2015 BUR V Y (55) (4) Y
INSPECTION COMMENTS: PANEL,KITCHEN AND LIVING RM ONLY INSPECTED
 
(5) 07/01/2015 07/08/2015 WYF C R (35) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M351894
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
KITCHEN RECEPTACLE IN ISLAND BASEBOARD NOT GFCI PROTECTION. 210.88
RSLV 04/10/2015 04/10/2015 05/19/2015
 
002 (999) OTHER
KITCHEN RECEPTACLES RECESSED INTO CABINET WOOD NO PROTECTIONPROVIDED 314.20.RE4CEP NOT SPACED PROPERLY AS PER ART 210.52
RSLV 04/10/2015 05/19/2015 07/01/2015
 
003 (999) OTHER
KITCHEN RECEPTACLE PROVIDED FOR ISLAND DOES NOT MEET CODEREQUIREMENT 210.52
RSLV 04/10/2015 04/10/2015 05/19/2015
 
004 (999) OTHER
KITCHEN CEILING: FLEXIBLE CORD NOT PERMITTED IN CEILING ON L.E.DDRIVERS. 400.8(2)
RSLV 05/19/2015 05/19/2015 07/01/2015
 
005 (999) OTHER
KITCHEN CEILING: DOUBLE LUGGING NOT LISTED UNDER THE SAME LUG FOR AC DISCONNECT.. 110.3B
RSLV 05/19/2015 05/19/2015 07/01/2015
 
006 (999) OTHER
KIT./LIV.RM: EXTENSION CORD USED AS PERMANENT WIRING FOR KITCHEN ANDLIVING RM T.V.. 400.8
RSLV 05/19/2015 05/19/2015 07/01/2015
 
007 (999) OTHER
PANELS: ARC FLASH STICKERS NOT PROVIDED ON PANELS.. 110.16
RSLV 05/19/2015 05/19/2015 07/01/2015