| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE (ALL FLOORS) THE ENTIRE STORE FRONTCOM: REMOVED & INSTALLED TEMPORARY WIRING, BRANCH CIRCUIT WIRING |
RSLV |
03/19/2014 |
03/19/2014 |
06/26/2019 |
| |
| 002 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE (ALL FLOORS) RECEPTACLE OUTLETS, LIGHTING FIXTURESTHIS IS NOT A FINAL INSPECTION. SEE THIS COMPLAINT #1367604 |
RSLV |
03/19/2014 |
03/19/2014 |
06/26/2019 |
| |
| 003 |
(999) |
OTHER (FLOOR: 002) KITCHEN EMT NEEDS STRAP 358.30 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 004 |
(999) |
OTHER (FLOOR: 002) CEILING LIGHT KITCHEN WIRED WITH FLEX CORD 400.8 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 005 |
(999) |
OTHER (FLOOR: 002) SCONCE LIGHTS GROUNDS CUT 250 410.44 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 006 |
(999) |
OTHER (FLOOR: 002) EXPOSED WIRING METHOD COOKING HOOD 300.22 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 007 |
(999) |
OTHER (FLOOR: 002) HANDLE TIES FOR PANEL 210.4 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 008 |
(999) |
OTHER (FLOOR: 002) DISHWASHER DISCONNECT ACCESS 404.8 110.26 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS) UPSTAIRS KITCHEN AND FRONT COVER MISSING 314.25 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 010 |
(999) |
OTHER (GROUND FLOOR) KO OPEN IN PANEL 110.12 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 011 |
(999) |
OTHER (GROUND FLOOR) GFI NEEDED WHERE MISSING KITCHEN AREA 210.8 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |
| |
| 012 |
(999) |
OTHER (GROUND FLOOR) EXT COLLAR FOR BOX SET IN WOOD 314.20 |
RSLV |
09/25/2018 |
09/25/2018 |
06/26/2019 |