BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M351082
Premises: 54 WEST 14 STREET MANHATTAN BIN: 1009709     Block: 577   Lot: 13
   
Application Completed and Certified

Filed: 54 W 14 ST Census Tract:   63 Health Area:  5700
ENTIRE STORE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 02/06/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/05/2014 6:11 PM
Application Entered:   03/05/2014 Job Start Date:   03/05/2014
Last Change:   02/06/2015 Job End Date:   03/04/2015
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     01/13/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011041 Licensee Name: SALVATORE CHIARAMONTE
Firm: 003893 Firm Name: L&B ELEC'L INTERNATIONAL
Firm Phone: 347-295-0380  Firm Address: 150-50 11TH AVENUE WHITESTONE NY 11357 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $460.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   DAIRY QUEEN
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID WEINNMAN
Owner Business Name: FAB 14 LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  3  3#3/0THNNX3TIMES
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  3#3/0THNNX3TIMES
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  3#3/0THNNX3TIMES
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS      15                   
001    45  55    15             
002    25  15               
Buildings Total 70  85    12  23                
Total Units : 190 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/17/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M351082
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/10/2014 06/17/2014 IOS V (85) (5) Y
INSPECTION COMMENTS: REFFERED TO ENFORCEMENT FOR 3 NEW SERVICE SWITCHES
 
(2) 01/13/2015 01/17/2015 ECH C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M351082
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1ST FLOOR CONDUIT IN HOOD AREA FOR LIGHTING. 300.22
RSLV 06/10/2014 06/10/2014 01/13/2015
 
002 (999) OTHER
CELLAR MORE THAN ALLOWABLE # OF CONDUCTORS IN 1 INCH CONDUIT ONPANEL ON RIGHT SIDE. ANNEX C TABLE C1
RSLV 06/10/2014 06/10/2014 01/13/2015
 
003 (999) OTHER
CELLAR TWO MANY WIRES IN 1 INCH CONDUIT IN EXISTIONG PANEL ANNEXTABLE C1
RSLV 06/10/2014 06/10/2014 01/13/2015
 
004 (999) OTHER
CELLAR NO GROUPING 210.4 (D) ALL PANELS
RSLV 06/10/2014 06/10/2014 01/13/2015
 
005 ( 32) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN JUNCTION BOX
CELLAR 12X12 SPLICE BOX IS OVERFILLED
RSLV 06/10/2014 06/10/2014 01/13/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.