| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
600 AMP SWITCH |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
2 |
2 SET OF 350 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE BSMT SERVICE EQUIPMENT 600 AMP SERVICE SW, SERV. ENTCOM: 600 AMP SERV, SWITCH, ONE SET OF 500 MCM "ALSO OBSERVE". 1) THE |
RSLV |
02/26/2014 |
02/26/2014 |
07/09/2015 |
| |
| 002 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE BONDING & GROUNDING JUMPER IS UNDER SIZE, 2) WATER MAIN CONDUCTOR ISNOT CONTINUOUS AT THE WATER PIPE |
RSLV |
02/26/2014 |
02/26/2014 |
07/09/2015 |
| |
| 003 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE THIS IS NOT A FINAL INSPECTION. SEE THIS COMPLAINT #1366268 |
RSLV |
02/26/2014 |
02/26/2014 |
07/09/2015 |
| |
| 004 |
(999) |
OTHER CELLAR: DISCONNECT DOOR CANNOT OPEN PROPERLY AT 90 DEGREE 110.26 |
RSLV |
07/09/2015 |
07/09/2015 |
07/29/2015 |
| |
| 005 |
(999) |
OTHER CELLAR: SUPPLEMENTAL GROUND NOT PROVIDED FOR SERVICE SWITCH 250.53 |
RSLV |
07/09/2015 |
07/09/2015 |
07/29/2015 |
| |
| 006 |
(999) |
OTHER DISCONNECT: METAL RACEWAY LACKS ELECTRICAL CONTINUITY 300.10 |
RSLV |
07/09/2015 |
07/09/2015 |
07/29/2015 |
| |
| 007 |
(999) |
OTHER WATER METER NOT JUMPED PROPERLY 250.53CELLAR: |
RSLV |
07/09/2015 |
07/09/2015 |
07/29/2015 |
| |
| 008 |
(999) |
OTHER CELLAR SERVICE EQUIPMENT NOT BONDED PROPERLY 250.92A |
RSLV |
07/09/2015 |
07/09/2015 |
07/29/2015 |
| |
| 009 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE (ALL FLOORS)CELLAR: EL.RM: 600A S.SW CORRODED AND ALTERATED AM 110.2, 300.6 |
RSLV |
07/29/2015 |
07/29/2015 |
03/09/2016 |
| |
| 010 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ALL FLOORS)CELLAR: EL RM EMT FOR GEC TO 600A S.SW NOT SECURED 358.30 |
RSLV |
07/29/2015 |
07/29/2015 |
03/09/2016 |