BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M350796
Premises: 1147 2 AVENUE MANHATTAN BIN: 1078347     Block: 1415   Lot: 21
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1143 2 AV Census Tract:   110 Health Area:  4900
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):   EAST 60 STREET,    EAST 61 STREET
Status:   C - JOB IS SIGNED OFF 05/20/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/26/2014 10:33 PM
Application Entered:   02/26/2014 Job Start Date:   02/26/2014
Last Change:   05/20/2016 Job End Date:   06/20/2014
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     05/19/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011398 Licensee Name: JOSEPH FERGUSON
Firm: 003192 Firm Name: AVALON ELECTRIC CORP.
Firm Phone: 718-543-2327  Firm Address: 5760 BROADWAY 2ND FLOOR BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,210.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (14  Stores, 65 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES BUSH
Owner Business Name: 1143 SECOND LLC
Authorized Representative:  JAMES BUSH
Relationship To Owner:   MANAGING AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  ..........2-600AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  2 SETS OF #6 AND #2 EACH
B. Over #2 to 1/0  2  2 SETS OF #1
C. Over 1/0 to 250 MCM  2  1 SET #4/0 , 1 SET #3/0
D. Over 250 MCM  10  2 SETS #300/ 8 SETS #400
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 3 #10-Wire 3
Existing Meters 14 + New Meters 14 - Removed Meters 14 = Total Meters 14

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/26/2014 Notice: 1 - FIRST NOTICE 04/19/2016
Power Issued: 02/26/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING NEW SERVICE, METERS AND SWITCHES FOR THE RETAIL SPACES.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M350796
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/27/2015 07/30/2015 UMS A E (135) (5) Y
INSPECTION COMMENTS: 2 600A SERVICE SWITCHES,13 DISCONNECT SWITCHES RATED AT 60A TO 400A SEE APP CHANGES
 
(2) 04/18/2016 04/19/2016 EDB V Y (55) (1)
INSPECTION COMMENTS: P
 
(3) 05/19/2016 05/20/2016 TUR C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED , INSPECTION COMPLETE

OBJECTION FOR APPLICATION #: M350796
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) SERVICE SWITCHES NOT GROUNDED.. 250.24
RSLV 07/27/2015 07/27/2015 04/18/2016
 
002 (999) OTHER
(ALL FLOORS)SERVICE RACEWAY ON THE SUPPLY SIDE NOT BONDED PROPERLY.. 250.102C
RSLV 07/27/2015 07/27/2015 04/18/2016
 
003 (999) OTHER
(ALL FLOORS) SERVICE DISCONNECT SWITCHES NOT MARKRD.. AMEND 230.70
RSLV 07/27/2015 07/27/2015 04/18/2016
 
004 (999) OTHER
(ALL FLOORS) 400 AMD DISCONNECT SWITCH MISSING KO SEAL.. 110.12A
RSLV 07/27/2015 07/27/2015 04/18/2016
 
005 (999) OTHER
(ALL FLOORS)NO PLAQUE PROVIDED AT SERVICE DISCONNECT LOCATIONS TO SHOW REST OFSERVCE AND DISCONNECTS.. 230.2E
RSLV 07/27/2015 07/27/2015 05/19/2016
 
006 ( 10) BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE
(BASEMENT) 200 A SW. : # 4 AWG ON 175 A FUSE 310.16
RSLV 04/18/2016 04/18/2016 05/19/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.