BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M350380
Premises: 419 EAST 70 STREET MANHATTAN BIN: 1045815     Block: 1465   Lot: 14
   
Application Completed and Certified

Filed: 419 E 70 ST Census Tract:   124 Health Area:  4300
1ST FLOOR STORE Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):    1 AVENUE,    YORK AVENUE
Status:   C - JOB IS SIGNED OFF 07/22/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/17/2014 2:53 PM
Application Entered:   02/17/2014 Job Start Date:   02/18/2014
Last Change:   07/22/2014 Job End Date:   06/05/2014
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     06/25/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011616 Licensee Name: CESAR TIPIAN
Firm: 004145 Firm Name: C.T.C. ELEC'L CONTRS INC
Firm Phone: 347-810-9954  Firm Address: 435 AUSTIN PLACE, SUITE D BRONX NY 10455 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $76.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   DELI
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: XAVIER HERRERA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    42  50    12  42         
Buildings Total 42  50    12  42              
Total Units : 154 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/16/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REMAIN EXISTING ELECTRIC SERVICE AND CB PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M350380
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/06/2014 06/16/2014 LBI V (45) (3) Y
INSPECTION COMMENTS: VIOL
 
(2) 06/25/2014 07/08/2014 ECH C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M350380
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
1FL/ GFCI NOT PROVIDED FOR ALL FOOD PREP RECEPT NEAR SINKS 210.8B
RSLV 06/06/2014 06/06/2014 06/25/2014
 
002 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
1FL/DEFECTIVE EGC TERMINATION IN ALL DISCONNECTS IN REAR YARD 250.8
RSLV 06/06/2014 06/06/2014 06/25/2014
 
003 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
1FL/EGC UNDERSZ AT AC COMPRESSOR IN REAR FOR 30A CKT TABLE 250.122
RSLV 06/06/2014 06/06/2014 06/25/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back