Premises: 505 EAST 89 STREET MANHATTAN BIN: 1051369     Block: 1586   Lot: 5
   
Application Completed and Certified

Filed: 515 E 89 ST Census Tract:   152 Health Area:  3300
APT. 1E Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   YORK AVENUE,    EAST END AVENUE
Status:   C - JOB IS SIGNED OFF 06/08/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/16/2014 9:18 AM
Application Entered:   02/16/2014 Job Start Date:   02/17/2014
Last Change:   06/08/2015 Job End Date:   04/17/2014
Appointment Status:   
Last Inspection By:   URIM SYLA       On     06/03/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010641 Licensee Name: WILLIE THROWER, JR.
Firm: 002858 Firm Name: NOBLE ELECL CONTRG CO INC
Firm Phone: 718-299-9472  Firm Address: 1794 CLINTON AVENUE BRONX NY 10457 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $56.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MATHEW LOMBARDI
Owner Business Name: OWNER
Authorized Representative:  MATHEW LOMBARDI
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1E             
Buildings Total               
Total Units : 17 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/19/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RELOCATE KITCHEN AND PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M350367
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/10/2014 11/19/2014 UMS A (35) (2) Y
INSPECTION COMMENTS: NONE
 
(2) 06/03/2015 06/08/2015 UMS C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M350367
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
HALLWAY: NO HANDLE TIES PROVIDED FOR MULTIWIRE BRANCH CIRCUITS210.4
RSLV 11/10/2014 11/10/2014 06/03/2015
 
002 (999) OTHER
PANEL: PANEL NOT GROUNDED PROPERLY. EGC RUN THROUGH FMC NOT GROUND-ING THE PANEL. 408.40
RSLV 11/10/2014 11/10/2014 06/03/2015