Electrical Application Details for App #: M350324
Premises: 131 EAST 23 STREET MANHATTAN BIN: 1018040     Block: 879   Lot: 17
   
Application Completed and Certified

Filed: 131 E 23 ST Census Tract:   68 Health Area:  5300
GROUND FLOOR,BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10010 Community Board:   105
Related Job Number:    121406692
DOB Cross Street(s):   PARK AVENUE SOUTH,    LEXINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 03/14/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/13/2014 5:28 PM
Application Entered:   02/13/2014 Job Start Date:   02/14/2014
Last Change:   03/14/2015 Job End Date:   02/12/2015
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     02/04/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011621 Licensee Name: JAMES P RYAN
Firm: 003160 Firm Name: J.P. RYAN ELECTRIC, INC.
Firm Phone: 718-393-7516  Firm Address: 38-32 29TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $268.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121406692
Building Used As:   Z - Other
Store / Other:   BANK
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT WALSH
Owner Business Name: TD BANK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  3/0
D. 3 Phase Over 225 AMPS  1  600MCM
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    24  26  22         
GND    60  48  22     
Buildings Total 84  74  44            
Total Units : 224 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/22/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M350324
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/12/2014 09/17/2014 EID A (60) (4) Y
INSPECTION COMMENTS: NOT INSPECTED: ALL A/C EQUIPMENT IN 1ST FLOOR AND LIGHTING ON 1ST FLOOR
 
(2) 10/22/2014 10/28/2014 EID A Y (60) (2) Y
INSPECTION COMMENTS: NONE
 
(3) 12/01/2014 12/05/2014 EDB A Y (45) (4) Y
INSPECTION COMMENTS: NO ACCESS TO A/C EQUIPMENT 005,006
 
(4) 12/26/2014 01/06/2015 EID N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW - CALLED NO ANSWER
 
(5) 01/20/2015 01/22/2015 NRS V Y (55) (0) Y
INSPECTION COMMENTS: A/C EQUIPMENT NOT INSPECTED ON 1ST FLOOR
 
(6) 02/04/2015 02/11/2015 ECH C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M350324
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT NO SQUARE OF GROUND FOR ISOLATED GROUND BAR IN PANEL(250.112)
RSLV 09/12/2014 09/12/2014 10/22/2014
 
002 (999) OTHER
BASEMENT EGC COND. DOUBLED UP IN BASEMENT A/C DISC (110.14 (A)
RSLV 09/12/2014 09/12/2014 10/22/2014
 
003 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
BASEMENT SERVICE RECEP NOT PROVIDED FOR A/C EQUIP (210.63)
RSLV 09/12/2014 09/12/2014 10/22/2014
 
004 (999) OTHER
BASEMENT OVER 31 CURRENT CARRYING COND IN TROUGH (310.15B(2A)
RSLV 09/12/2014 10/22/2014 12/01/2014
 
005 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
1ST FL NO SERVICE RECEP PROVIDE AT A/C UNITS 210.63
RSLV 10/22/2014 12/01/2014 01/20/2015
 
006 (999) OTHER
1ST FL A/C UNITS NOT SPEC. AS PER MAN SPEC. 110.3
RSLV 10/22/2014 12/01/2014 01/20/2015
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT: EMT NOT PROPERLY SECURED (EL RM). 358.30
RSLV 12/01/2014 12/01/2014 01/20/2015
 
008 (999) OTHER
BSMT: PANELS MULTIWIRE CKT NO GROUPED,NO SIMULT TRIP. 210.4
RSLV 12/01/2014 01/20/2015 02/04/2015
 
009 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT: EL.RM. FMC NO EQUIPMENT GND. 250.118,112
RSLV 12/01/2014 12/01/2014 01/20/2015
 
010 (999) OTHER
BSMT: EL.RM/METER RM PULL BOX TOO SMALL. 314.28
RSLV 12/01/2014 12/01/2014 01/20/2015