BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M350171
Premises: 64 WOOSTER STREET MANHATTAN BIN: 1007281     Block: 486   Lot: 2
   
Application Completed and Certified

Filed: 64 WOOSTER ST Census Tract:   49 Health Area:  6800
CELLAR, GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   BROOME STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 09/20/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/10/2014 11:58 AM
Application Entered:   02/10/2014 Job Start Date:   02/10/2014
Last Change:   09/20/2014 Job End Date:   02/10/2015
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     09/04/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012295 Licensee Name: ADAM MONAHAN
Firm: 004377 Firm Name: M.C. ELECTRICAL NY INC
Firm Phone: 929-296-0197  Firm Address: 50-10 49TH STREET, UNIT 1 WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $255.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SIMON ZAR
Owner Business Name: 64-68 WOOSTER, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  225A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    50  25                   
GND    60  30                 
Buildings Total 110  55                    
Total Units : 171 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/06/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M350171
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/01/2014 08/06/2014 NRS V (80) (6) Y
INSPECTION COMMENTS: NOT INSPECTED: A/C , LIGHTS, PIT. TOP OF CAR
 
(2) 09/04/2014 09/09/2014 EID C R (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M350171
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
BASEMENT KITCHEN UCL
RSLV 08/01/2014 08/01/2014 09/04/2014
 
002 (999) OTHER
GROUND KITCHEN COUNTER OUTLET BOXES SET TOO DEEP IN COMB 314.20
RSLV 08/01/2014 08/01/2014 09/04/2014
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND AIR CURTAINS AND DISCONNECTS
RSLV 08/01/2014 08/01/2014 09/04/2014
 
004 (999) OTHER
GROUND FRONT DESK RECEPTICLE BOXES SET TOO DEEP IN COMBUSTIBLE314.20
RSLV 08/01/2014 08/01/2014 09/04/2014
 
005 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
GROUND CEILING LED STRIP LIGHTS ABOVE STAIRS
RSLV 08/01/2014 08/01/2014 09/04/2014
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASE ELEVATOR CONTROLLER EGC NONT AS PER 250.122 # AWG GROUND FOR30A OC PC
RSLV 08/01/2014 08/01/2014 09/04/2014