| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
3-#3 AWG |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
12/24 CKT, MAIN LUG 100A |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER 1 FL: MISSING RECEPTICAL. 210.52 |
OPEN |
03/13/2014 |
03/13/2014 |
|
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED T-OUT: OUTLET BOX(S) MISSING COVERS, 314.25 |
OPEN |
03/13/2014 |
03/13/2014 |
|
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED PANEL: AFCI NOT PROVIDED. 210.12 |
OPEN |
03/13/2014 |
03/13/2014 |
|
| |
| 004 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE T-OUT: OPEN WIRING. AMD. 110.2A |
OPEN |
03/13/2014 |
03/13/2014 |
|
| |
| 005 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED T-OUT: LIGHT FIXTURE NOT BONDED/GND. 250.4 |
OPEN |
03/13/2014 |
03/13/2014 |
|
| |
| 006 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT: AC CABLE NOT PROPERLY SECURED. 348.30 |
OPEN |
03/13/2014 |
03/13/2014 |
|
| |
| 007 |
( 53) |
GFCI HAS NOT BEEN PROVIDED OUTDOOR: NO GFCI PROVIDED (BACK YARD). 210.8 |
OPEN |
03/13/2014 |
03/13/2014 |
|
| |
| 008 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED BSMT: NO WORKING SPACE IN FRONT OF ELECT. EQUIPMENT. 110.26 |
OPEN |
03/13/2014 |
03/13/2014 |
|