| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200 A |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
4#2 |
| B. Over #2 to 1/0 |
1 |
4- 3/0 |
| C. Over 1/0 to 250 MCM |
2 |
2-350 MCM |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
12 POLE PANEL |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)BASEMENT BONDING LOCK NUT NOT PROPERLY BONDED TO SERVICE EQUIPMENTS250.92A |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS)BASEMENT END LINE BOX NOT PEOPERLY BONDED 250.92A 250.80 |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS)BASEMENT GROUNDING ELECTRODE NOT PEOPERLY TERMINATED TO BEAM WITHCLAMP 250.8 |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)BASEMENT ARC FLASH STICKERS MISSING IN EWUIPMENTS 110.16 |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS) BASEMENT EMT PIPE NOT STRAPPED 358.30 |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS) BASEMETN NEUTRAL NOT BONDED IN SERVICE SWITCH |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) STAIRWAY NO FIRESTOPPING PROVIDED FOR RISER 300.21 |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS)BASEMENT INSUFFICIENT WORKING CLEARANCE IN FRONT OF 200 AMPDICONNECT 110.26 |
RSLV |
07/17/2015 |
07/17/2015 |
09/01/2016 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS)BASEMENT NO GROUNDING ELECTRODE AND SUPPLENTRY END PROVIDED FOR 200AMP SERVICE DISCONNECT 250.64 |
RSLV |
07/17/2015 |
07/17/2015 |
04/15/2016 |
| |
| 010 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ALL FLOORS) RISER |
RSLV |
04/15/2016 |
04/15/2016 |
09/01/2016 |
| |
| 011 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ELEVATOR PIT) COMBO PORCELAIN BASE |
RSLV |
04/15/2016 |
04/15/2016 |
09/01/2016 |