BIS Menu  |  Applications  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M349850
Premises: 87 CHAMBERS STREET MANHATTAN BIN: 1089729     Block: 149   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 87 CHAMBERS ST Census Tract:   21 Health Area:  7700
BROADWAY & CHURCH STREET Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
DOB Cross Street(s):   BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 02/10/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/30/2014 12:49 PM
Application Entered:   01/30/2014 Job Start Date:   01/30/2014
Last Change:   02/10/2017 Job End Date:   12/25/2014
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     02/09/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN MOORE
Owner Business Name: CM&ASSOCIATES CONSTRUCTIO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  250.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 10/17/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:   DEVICE NO. PE1 & PE2

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M349850
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/06/2015 07/10/2015 EID A (60) (5) Y
INSPECTION COMMENTS: 1P48009,48002
 
(2) 06/16/2016 06/21/2016 BMP J Y (35) (0)
INSPECTION COMMENTS: JOB IN PROGRESS.
 
(3) 10/14/2016 10/17/2016 STP L X (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NEEDS TO FILE FOR CORRECT ADDRESS. LOCATION PROBLEM. ADDRESS IS 71 READE ST WHICH DOES NOT SHARE WITH 87 CHAMBERS
 
(4) 02/09/2017 02/10/2017 TOR C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS ONLY

OBJECTION FOR APPLICATION #: M349850
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)PE2 CONTROL ROOM: ELEVATOR MOTORS OVER FUSE ON 100 AMP.. 240.3
RSLV 07/06/2015 07/06/2015 06/16/2016
 
002 (127) NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM
(ALL FLOORS)CELLAR: 16 KVA TRANSFORMER,NO GEC PROVIDED FO STEEL OR WATER BOTHROOM (2).. 250.20
RSLV 07/06/2015 07/06/2015 02/09/2017
 
003 (999) OTHER
(ALL FLOORS) PIT: LIGHT AND G.F.C.I.SHARE SAME CIRCUIT.. 620.24
RSLV 07/06/2015 07/06/2015 06/16/2016
 
004 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ALL FLOORS) TOP OF CAR: NON FUNCTIONAL G.F.C.I.. AMEND 110.2(A)
RSLV 07/06/2015 07/06/2015 06/16/2016
 
005 ( 17) DEFECTIVE SWITCHES ARE IN USE
(ALL FLOORS) TOP OF CAR: NON FUNCTIONAL LIGHT.. AMEND 110.2(A)
RSLV 07/06/2015 07/06/2015 06/16/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.