BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M349827
Premises: 10 EAST 52 STREET MANHATTAN BIN: 1035478     Block: 1287   Lot: 63
   
Application Completed and Certified

Filed: 10 E 52 ST Census Tract:   102 Health Area:  4800
3RD FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   CARTIER-RICHEMONT
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 11/06/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/29/2014 5:30 PM
Application Entered:   01/29/2014 Job Start Date:   01/29/2014
Last Change:   11/06/2014 Job End Date:   04/18/2014
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     09/18/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011229 Licensee Name: RICHARD SOBEL
Firm: 002851 Firm Name: QUANTUM ELECTRIC CORP.
Firm Phone: 718-784-9010  Firm Address: 41-11 28TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $126.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121892452
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TISHMAN SPEYER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4#4
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  (1) 100A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    12  33    46             
Buildings Total 12  33    46                
Total Units : 94 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/29/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RICHEMONT 3RD FLOOR QEC #9107

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M349827
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/23/2014 07/29/2014 PHG A (55) (8) Y
INSPECTION COMMENTS: NONE
 
(2) 09/18/2014 09/24/2014 DNM C R (25) (0) Y
INSPECTION COMMENTS: OBJECTION #5 DONE BY STHERS, ELECTRICIANS NOT IN, SCOPE OF WORK

OBJECTION FOR APPLICATION #: M349827
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
3FL: NO G.F.C.I.PROVIDED IN PANTRY. 210.8
RSLV 07/23/2014 07/23/2014 09/18/2014
 
002 (999) OTHER
3FL:ALL LED LIGHTS LINE AND LOW VOLT IN SAME BOX. ART.725
RSLV 07/23/2014 07/23/2014 09/18/2014
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
3FL: NO DIRECTORY FOR PANEL. 408.4
RSLV 07/23/2014 07/23/2014 09/18/2014
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
3FL: KO MISSING IN PANEL. 110.2
RSLV 07/23/2014 07/23/2014 09/18/2014
 
005 (999) OTHER
3FL: BX SLEEVED THRU PIPE IN IT CLOSET. 300.10
RSLV 07/23/2014 07/23/2014 09/18/2014
 
006 ( 29) OUTLET BOXES ARE NOT COVERED
3FL: OPEN BOXES IN CEILING T-OUT. 314.25RECEPTACLES NOT GRND/BOND MC CABLE. 250.146
RSLV 07/23/2014 07/23/2014 09/18/2014
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
3FL: NYC FURNITURE BOX NOT BONDED. 250.112
RSLV 07/23/2014 07/23/2014 09/18/2014
 
008 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
3FL: EMT PIPE NOT SUPPORTED IN OFFICE SPACE CEILING. 358.30
RSLV 07/23/2014 07/23/2014 09/18/2014