| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
4#4 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
(1) 100A |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 3FL: NO G.F.C.I.PROVIDED IN PANTRY. 210.8 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |
| |
| 002 |
(999) |
OTHER 3FL:ALL LED LIGHTS LINE AND LOW VOLT IN SAME BOX. ART.725 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY 3FL: NO DIRECTORY FOR PANEL. 408.4 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |
| |
| 004 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX 3FL: KO MISSING IN PANEL. 110.2 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |
| |
| 005 |
(999) |
OTHER 3FL: BX SLEEVED THRU PIPE IN IT CLOSET. 300.10 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |
| |
| 006 |
( 29) |
OUTLET BOXES ARE NOT COVERED 3FL: OPEN BOXES IN CEILING T-OUT. 314.25RECEPTACLES NOT GRND/BOND MC CABLE. 250.146 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |
| |
| 007 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 3FL: NYC FURNITURE BOX NOT BONDED. 250.112 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |
| |
| 008 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) 3FL: EMT PIPE NOT SUPPORTED IN OFFICE SPACE CEILING. 358.30 |
RSLV |
07/23/2014 |
07/23/2014 |
09/18/2014 |